Richmond 12GRX40-40F Encore 40 Gallon 40,000 BTU Tank Natural Gas Water Heater

Use & Care Manual - Page 8

For 12GRX40-40F.

PDF File Manual, 28 pages, Read Online | Download pdf file

12GRX40-40F photo
Loading ...
Loading ...
Loading ...
8
Installing the water heater.
Combustion and Ventilation Air
Proper operation of the water heater
requires air for combustion and
ventilation. Provisions for combustion
and ventilation air must comply with
referenced codes and standards.
When installed in a closet, DO NOT
block or obstruct any of the combustion
air inlet openings located around
the perimeter of the water heater. A
minimum of 1” is required between
these combustion air inlet openings and
any obstruction.
NOTICE: If the water heater is
installed in an unconfined space within a
building of conventional frame, masonry
or metal construction, infiltration
air is normally adequate for proper
combustion and ventilation. If the
water heater is installed in a confined
space, provisions for combustion and
ventilation air must be made.
A confined space is one having a volume
of less than 50 cubic feet per 1,000 Btuh
of the aggregate input of all appliances
within that space.
The air must be supplied through two
permanent openings of equal area. One
is to be located within 12” above the floor
and the other is to be located within 12”
from the ceiling.
The minimum net free area of each opening
must not be less than one square inch
per 1,000 Btuh of the total input rating
of all the appliances in the enclosure
(but not less than 100 square inches), if
each opening communicates with other
unconfined areas inside the building.
Buildings of unusually tight construction
shall have the combustion and ventilation
air supplied from outdoors, or a freely
ventilated attic or crawl space.
If air is supplied from outdoors, directly or
through vertical ducts, there must be two
openings located as specified above and
each must have a minimum net free area
of not less than one square inch per 4,000
Btuh of the total input rating of all the
appliances in the enclosure.
If horizontal ducts are used to
communicate with the outdoors, each
opening must have a minimum net free
area of not less than one square inch per
2,000 Btuh of the total input rating of all
the appliances in the enclosure. If ducts
are used, the minimum dimensions of
rectangular air ducts shall not be less than
3”.
NOTICE: If the duct openings which
supply combustion and ventilation air
are to be covered with a protective
screen or grill, the net free area
(openings in the material) of the
covering material must be used in
determining the size of the openings.
Protective screening for the openings
MUST NOT be smaller than 1/4” mesh
to prevent clogging by lint or other
debris.
Corrosive Atmospheres
The air in beauty shops, dry cleaning
establishments, photo processing
labs, and storage areas for liquid and
powdered bleaches or swimming pool
chemicals often contain such halogenated
hydrocarbons.
An air supply containing halogenated
hydrocarbons may be safe to breathe,
but when it passes through a gas flame
corrosive elements are released that
will shorten the life of any gas burning
appliance.
Propellants from common spray cans
or gas leaks from A/C and refrigeration
equipment are highly corrosive after
passing through a flame.
The water heater warranty is voided when
failure of the heater is due to operation in
a corrosive atmosphere.
NOTICE: The water heater
should not be installed near
an air supply containing
halogenated hydrocarbons.
Inspect Shipment
Inspect the water heater for possible
damage. Check the markings on the rating
plate of the water heater to be certain the
type of gas supplied corresponds to the
water heater requirements.
Loading ...
Loading ...
Loading ...