ELECTRICAL REQUIREMENTS
Use ONLYthe wiring size recommended for single
outlet branch circuit.
Proper current protection isthe responsibility
of the owner.
Recommended branch circuit wire sizes*
Nameplate
maximum circuit AWG Wire
breaker size size**
!5A 14
20A 12
30A 10
AWG- AmericanWireGauge
* Singlecircuitbreakerfrommainbox
** Basedoncopperwire,singleinsulatedconductorat60° C
NOTE: Use copper conductors only.
2:30/208 VOLT
ELECTRICAL SUPPLY
A power supply kit must be usedto supply power
to the Zonelineunit.Theappropriatekit isdetermined
bythe voltage, the means of electrical connection
and the amperage ofthe branch circuit. Seethe
POWERCONNECTIONCHARTon page 1:3to selectthe
appropriate kit.
Power supply kit
All wiring, including installation of the receptacle,
must be in accordance with the NECand local codes,
ordinances and regulations.
@ @ @
Tandem Perpendicular Large Tandem
15 Amp 20 Amp 30 Amp
230/208 volt receptacle configuration
FOR 230/208 VOLT CORD
CONNECTIONS ONLY
1. Removethe front panel by taking out the four
front screws,the upper two screws from the top
of the panel and the shipping screws on each side,
if present.(Discardthe four sideshipping screws,
if present.)
Side
-..._ shipping
screw
/
2. Removethe junction box cover and the junction box
and discard.
Remove
junction box
and cover
3. Connectthe power cord, with a loop,through
the strain relief.
relief
III PORTANT:
Powercord must
havea loop.
11