7.4 Turn Off Operation
7.4.1 Turn Off Operation in Line Mode
WARNING: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown,
confirm all power loads are turned off.
The LCD diagrams shown below are when the UPS is operating in Line Mode.
Step 1: Stop the inverter. Press the “Power On/Off” button for 2 seconds until a beep is heard to turn off the UPS, or use the Menu-
Control-System. The UPS will transfer to Bypass Mode – or Standby Mode if the Bypass Mode setting is disabled.
7. UPS Operation
Power On/O󰀨 button