Tripp Lite S3M120KX SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 59

For S3M120KX. Series: S3MX
Also, The document are for others Tripp Lite models: S3MX *, S3M100KX, S3M100KXD, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
59
7. UPS Operation
7.3.2 Transfer Critical Load from Maintenance Bypass to Line Mode
Step 1
Turn ON the battery breaker (external battery cabinet).
Step 2 Single input model:
Turn ON the Q1 Input 1 breaker.
Single input model:
Turn ON the Q1 Input 1 breaker.
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker.
00KVA/120KVA
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker
160KVA/200KVA
Step 3
Go to the LCD INFORMATION Menu. Choose “SYSTEM” to ensure that Bypass Mode is enabled (“Power By Bypass”). If
Bypass Mode is disabled, set it to “enabled” through the SETUP menu and confirm the UPS is operating in Bypass Mode
before proceeding.
Step 4
Turn ON the Q3 Output breaker.
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100kVA/120kVA) Models
Turn ON the Q3 Output breaker.
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
S3M100KX
S3M120KX
(100 kVA/200 kVA) Models
S3M160KX
S3M200KX
(160 kVA/200 kVA) Models
Q1
Input 1
Q1
Input 1
Q1
Input 1
Q1
Input 1
Q2
Input 2
Q2
Input 2
S3M100KXD
S3M120KXD (100 kVA/200 kVA) Models
S3M160KXD
S3M200KXD (160 kVA/200 kVA) Models
2018/01/01
Q3
Output
Q3
Output
Loading ...
Loading ...
Loading ...