4. Control Panel and LCD Operations
Table 4.4: Measurement Items
Submenu Item Explanation
Input
L-N Voltage (V) Input phase voltage (L1, L2, L3). Units: 0.1V.
Frequency (Hz) Input frequency (L1, L2, L3). Units: 0.1 Hz.
Output
L-N Voltage (V) Output phase voltage (L1, L2, L3). Units: 0.1V.
L-N Current (A) Output phase current (L1, L2, L3). Units: 0.1A.*
Frequency (Hz) Output frequency (L1, L2, L3). Units: 0.1 Hz.
Power Factor Output power factor (L1, L2, L3).
Bypass
L-N Voltage (V) Bypass phase voltage (L1, L2, L3). Units: 0.1V.
Frequency (Hz) Bypass frequency (L1, L2, L3). Units: 0.1 Hz.
Power Factor Bypass power factor (L1, L2, L3).
Load
Sout (kVA) Apparent power. Units: 0.1kVA.
Pout (kW) Active power. Units: 0.1kW.
Load Level (%) The percentage of connected load. Units: 1%.
Battery
Positive Voltage (V) Battery positive voltage. Units: 0.1V.
Negative Voltage (V) Battery negative voltage. Units: 0.1V.
Positive Current (A) Battery positive current. Units: 0.1A.
Negative Current (A) Battery negative current. Units: 0.1A.
Remain Time (Sec) Battery remaining runtime. Units: 1 sec.
Capacity (%) The percentage of the battery capacity. Units: 1%.
Test Result Battery test result.
Charging Status Battery charging status.
Temperature 01(°C) Temperature of external battery pack. Units: 0.1°C.
Temperature 02(°C) Temperature of external battery pack through extra communication card T1. Units: 0.1°C.
Temperature 03(°C) Temperature of external battery pack through extra communication card T2. Units: 0.1°C.
Temperature 04(°C) Temperature of external battery pack through extra communication card T3. Units: 0.1°C.
Temperature 05(°C) Temperature of external battery pack through extra communication card T4. Units: 0.1°C.
* Output current at zero load or low load may indicate up to 1% current flow on the display due to inverter activity. For load power readings, go to the LOAD
submenu on the display.
4.2.5. Setup Screen
Touch the to enter into the Setup submenu. It requires a password to access the General, SYSTEM, BATTERY and PRE-ALARM
submenus (as shown in Figures 4.10 and 4.11). The default password is 0000.
Figure 4.10 Setup Menu
GENERAL
SYSTEM
BATTERY
PRE-ALARM
PARALLEL
SETUP Enter Password