Tripp Lite S3M120KX SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 35

For S3M120KX. Series: S3MX
Also, The document are for others Tripp Lite models: S3MX *, S3M100KX, S3M100KXD, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
35
4.2.5.4 Pre-Alarm Screen
The Pre-Alarm Screen Setup and Setting options are shown in Figure 4.17 and Table 4.10. The Pre-Alarm Setting can be accessed in any
operation mode.
Figure 4.17 Setup-Pre-Alarm Screen
Table 4.10: Setup Pre-Alarm Setting List
Setting Item Sub Item Explanation
Line Voltage Range --
Set line voltage range:
Upper limit
• +5%
• +10%
• +15%
• +20% (Default)
Lower limit
• -5%
• -10%
• -15%
• -20% (Default)
Line Frequency
Range
--
Set line frequency range:
Upper / Lower limit
• +/- 1 Hz
• +/- 2 Hz
• +/- 3 Hz
• +/- 4 Hz (Default)
Load --
Set UPS overload percentage (40~100%)
• 100% (Default)
Set UPS load unbalance percentage (20~100%)
• 100% (Default)
4. Control Panel and LCD Operations