Split-Over Partition Wall Ceiling Installation
Indoor applications: Apply a continuous 3/8” bead of non-drying (butyl) sealant
is applied to the warm side of the wall to ceiling joint. Lock ceiling panels
together and align over partition wall. Once all ceiling panels are assembled and
aligned, lock the wall to the ceiling.
PARTITION WALL
CEILING
PANELS
COOLER
SIDE
FREEZER
SIDE
BUTYL
SEALANT
Outdoor applications: Apply butyl tape to the partition wall anchor plate. Lock
ceiling panels together and align over partition wall. Once all ceiling panels are
assembled and aligned, attach lag bolts through the ceiling cam lock hole into the
anchor plate.
3/8” LAG BOLTS THROUGH
MALE CAM LOCK HOLES
PARTITION WALL
ANCHOR
PLATE
CEILING
PANELS
BUTYL
REFRIGERATION
TAPE (SHIPPED
LOOSE)
CAUTION
Apply a continuous 3/8” bead of non-drying (butyl) sealant at all partition wall/ceiling
joints. Apply the sealant on the warm side of the panel or as specified on assembly
drawing. This sealant application will assist in maintaining the vapor barrier.
WARNING
The top panels on walk-in units are designed, at a minimum, for an allowable live load
of ten pounds per square foot as noted on submittal drawings and installation
instructions. Top panels are not designed as work platforms or for dry storage and
should not be used as such. Use in such a manner could damage the structural
integrity of the top panels and will void the manufacturer’s warranty.