3A. Models with Factory Connected Power
Supply Cord
NOTE: Some models may be equipped with a factory
connected three (3) conductor power supply cord.
Mobile home installation or areas where local codes do not
permit grounding through neutral, a four (4) conductor
power supplycord kit rated at 125/250 volts minimum, and
marked for use with ranges shall be used. See Range
Connection Opening Size Chart for cord kit ampere rating
information. Terminals on end of wires must be either
closed loop or open-end spade lugs with upturned ends.
3B. Models Requiring Power Supply Cord Kit
RISK OF FIRE OR ELECTRICAL SHOCK MAY OCCUR IF AN
INCORRECT SIZE RANGE CORD KIT IS USED, THE
INSTALLATION INSTRUCTIONS ARE NOT FOLLOWED OR
STRAIN RELIEF BRACKET IS DISCARDED.
This appliance may be connected by means of a power
supply cord. Only a power supply cord kit rated at 125/250
volts minimum, and marked for use with ranges shall be
used. See chart on page 3 for cord kit ampere rating
information. Cord must have either three (3) or four (4)
conductors. Terminals on end of wires must be either
closed loop or open-end spade lugs with upturned ends.
Cord must have strain relief clamp.
See section 5Afor 3-wire or section 5B for 4-wire connection.
4. Electrical Connection to Range
The rear access cover must be removed. To remove, loosen
center screw (one screw) and remove access cover. The
terminal block will then be accessible.
/
/
Access I"-""
Cover /
Rear
of Range
Range Connection Opening Size Chart
Refer to chart below for proper range connection opening size and power
supply cord kit ampere rating information. See serial plate on range for
kilowatt rating data.
See Serial Plate on Range for
KW Rating
120/240 Volts 120/208 Volts
Cord Kit
Ampere
Rating
Diameter (inches) of Range
connection Opening
Cord Kit Permanent Wiring
0-8.7 KW 0-7.8 KW 30 Amp 1-1/8 in. 7/8 in.
8.8-16.5 KW 7.9-12.5 KW 40 Amp 1-3/8 in. 1-1/8 in.
16.6-22.5 KW 12.6-18.5 KW 50 Amp 1-3/8 in. 1-3/8 in.
NOTE: Range is shipped from factory with 1-3/8" dia. hole
as shown. To use either 7/8" dia. hole or 1-1/8" dia.
knockouts:
1-1/8" Dia. 7/8" Dia.
Knockout Hole
(See Chart) (See Chart)
Mounting
Plate
1=3/8" Dia.
Hole
(See Chart)
Pocket
for Cable
Mounting Plate
If a different diameter hole is required, please follow
the steps below:
1. Using a 1/4" socket driver, remove eight (8) screws from
Rear Wall Shield to release from the unit (as shown).
Save the screws for step #7 below.
2. Again using the 1/4" socket driver, remove one (1) blunt
point screw used to secure the Cable Mounting Plate to
the Rear Wall Shield. Save the screws for step #6.
3. Remove the Cable Mounting Plate from the Rear Wall
Shield by sliding the plate out of the pockets.
4. Ifa 1-1/8"dia. holeisrequired,"punch-out"theknockout.
5. Rotate the plate 180 degrees so that the desired hole
is placed on top of the opening located on the bottom
flange of the Rear Wall Shield.
6. Slide the Cable Mounting Plate into the Rear Wall
Shield. Re-secure using the blunt point screw removed
from step #2 above.
7. Reassemble the Rear Wall Shield to the unit using eight
(8) screws removed from step #1 above.