6
Operation
7. UPS Battery Information
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x00BC 188 Battery voltage 0.1V
0x00BD 189 Battery piece number
0x00BF 191 Battery capacity %
0x00C0 192 Battery remain time Minutes
8. UPS Working Mode
Holding Register (Read Function 0x03)
Address
Description Unit
Hex Decimal
0x00D0 208 UPS Mode inquiry See Appendix 2
9. UPS Fault Information
Holding Register (Range 0x02A3 - 0x02AE, Read Function 0x03)
Address
Description UnitHex Decimal
0x02A3 675 Fault type See Appendix 3
0x02A4 676 Battery voltage before fault 0.1V
0x02A5 677 I/P frequency before fault 0.1 Hz
0x02A6 678 I/P voltage before fault 0.1V
0x02A7 679 Inverter O/P frequency before fault 0.1 Hz
0x02A8 680 Inverter O/P voltage before fault 0.1V
0x02A9 681 Negative Bus voltage before fault 0.1V
0x02AA 682 Positive Bus voltage before fault 0.1A
0x02AB 683 O/P load before fault 0.1V
0x02AC 684 O/P current before fault 0.1V
0x02AD 685 Temperature before fault 0.1°C
0x02AE 686 UPS running status before fault See Appendix 4
10. Setting Parameter Item
Holding Register (Read Function for 0x034A, 0x034B and 0x34E, Write Function 0x10 for range 0x034F - 0x351)
Address
Description Unit Notes* TypeHex Decimal
0x034A 842 High efficiency mode voltage High Loss point V N/A Read Only
0x034B 843 High efficiency mode voltage Low Loss point V N/A Read Only
0x034E 846 The bypass Freq. High Loss point 0.1 Hz N/A Read Only
0x034F 847
The bypass Freq. Low Loss point (560, 580 or 590 for 60 Hz)
(460, 480 or 490 for 50 Hz)
0.1 Hz 560 Read / Write
0x0350 848 The bypass voltage High Loss point (244, 254 or 264) V 264 Read / Write
0x0351 849 The bypass voltage Low Loss point (176, 186 or 196) V 176 Read / Write
*The unit must be in Bypass Mode for changes to take effect.