Tripp Lite MODBUSCARDSV Programmable RS-485 Management Accessory Card

Operation Manual - Page 3

For MODBUSCARDSV. Also, The document are for others Tripp Lite models: SVTX, S3MX

PDF File Manual, 44 pages, Read Online | Download pdf file

MODBUSCARDSV photo
Loading ...
Loading ...
3
Operation
2. Capability Setting
Holding Register (Range 0x000E - 0x000F, Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description Value 0/Value 1 Register ValueHex Decimal
0x000E 14
Bit15 = Enable/disable audible alarm 0:FALSE / 1:TRUE E:8000 / D:7FFF
Bit14 = Enable/disable battery mode audible warning 0:FALSE / 1:TRUE E:4000 / D:BFFF
Bit9 = Enable/disable battery deep discharge protect 0:FALSE / 1:TRUE E:200 / D:FDFF
Bit8 = Enable/disable battery low protect 0:FALSE / 1:TRUE E:100 / D:FEFF
Bit6 = Enable/disable bypass forbidding 0:FALSE / 1:TRUE E:40 / D:FFBF
Bit4 = Enable/disable inverter short clear function 0:FALSE / 1:TRUE E:10 / D:FFEF
Bit3 = Enable/disable bypass when device turn off 0:FALSE / 1:TRUE E:8 / D:FFF7
Bit2 = Enable/disable bypass audible warning 0:FALSE / 1:TRUE E:4 / D:FFFB
Bit1 = Enable/disable high efficiency mode 0:FALSE / 1:TRUE E:2 / D:FFFD
0x000F 15
Bit12 = Enable/disable converter mode 0:FALSE / 1:TRUE E:1000 / D:EFFF
Bit4-Bit10 =Reservation N/A N/A
3. Control Item
Holding Register (Range 0x001A, Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description Value 0/Value 1 Register ValueHex Decimal
0x001A 26
Bit15 = Disable buzzer 0:FALSE / 1:TRUE Y:8000
Bit14 = Enable buzzer 0:FALSE / 1:TRUE Y:4000
Bit13 = Test until battery low 0:FALSE / 1:TRUE Y:2000
Bit12 = Remote turn off UPS 0:FALSE / 1:TRUE Y:1000
Bit11 = Remote turn on UPS 0:FALSE / 1:TRUE Y:800
Bit10 = Cancel shutdown 0:FALSE / 1:TRUE Y:400
Bit9 = Cancel test 0:FALSE / 1:TRUE Y:200
Bit8 = 10 seconds test 0:FALSE / 1:TRUE Y:100
Bit7-Bit0 = Reservation N/A N/A