Tripp Lite MODBUSCARDSV Programmable RS-485 Management Accessory Card

Operation Manual - Page 2

For MODBUSCARDSV. Also, The document are for others Tripp Lite models: SVTX, S3MX

PDF File Manual, 44 pages, Read Online | Download pdf file

MODBUSCARDSV photo
Loading ...
2
1. Warning Item
Holding Register (Range 0x0000 - 0x0003, Read Function 0x03)
Addresses start at 0 and are numbered 1-16 address as 0-15.
Address
Description Value 0/Value 1Hex Decimal
0x0000 0
Bit15 = Alarm: Line phase error 0:FALSE / 1:TRUE
Bit14 = Alarm: Bypass phase error 0:FALSE / 1:TRUE
Bit13 = Alarm: Bypass frequency unstable 0:FALSE / 1:TRUE
Bit12 = Alarm: Battery low 0:FALSE / 1:TRUE
Bit11 = Alarm: Charger fail 0:FALSE / 1:TRUE
Bit10 = Alarm: Remote shut down 0:FALSE / 1:TRUE
Bit9 = Alarm: L1 IP fuse fail 0:FALSE / 1:TRUE
Bit8 = Alarm: L2 IP fuse fail 0:FALSE / 1:TRUE
Bit7 = Alarm: L3 IP fuse fail 0:FALSE / 1:TRUE
0x0001 1
Bit8 = Alarm: Line connect different 0:FALSE / 1:TRUE
Bit7 = Alarm: Bypass connect different 0:FALSE / 1:TRUE
Bit5 = Alarm: Parallel output load different 0:FALSE / 1:TRUE
Bit0 = Alarm: Parallel Bypass Forbidden setting different 0:FALSE / 1:TRUE
0x0002 2
Bit15 = Alarm: Parallel Converter Enable setting different 0:FALSE / 1:TRUE
Bit14 = Alarm: Parallel Bypass Freq. High Loss setting different 0:FALSE / 1:TRUE
Bit13 = Alarm: Parallel Bypass Freq. Low Loss setting different 0:FALSE / 1:TRUE
Bit12 = Alarm: Parallel Bypass Volt High Loss setting different 0:FALSE / 1:TRUE
Bit11 = Alarm: Parallel Bypass Volt Low Loss setting different 0:FALSE / 1:TRUE
Bit10 = Alarm: Parallel Line Freq. High Loss setting different 0:FALSE / 1:TRUE
Bit9 = Alarm: Parallel Line Freq. Low Loss setting different 0:FALSE / 1:TRUE
Bit8 = Alarm: Parallel Line Volt High Loss setting different 0:FALSE / 1:TRUE
Bit7 = Alarm: Parallel Line Volt Low Loss setting different 0:FALSE / 1:TRUE
Bit6 = Alarm: Locked in bypass after overload 3x in 30 min 0:FALSE / 1:TRUE
Bit5 = Alarm: Warning for 3-phase AC input current unbalance 0:FALSE / 1:TRUE
Bit4 = Alarm: Warning for battery fuse broken 0:FALSE / 1:TRUE
Bit3 = Alarm: Warning for Inverter intercurrent unbalance 0:FALSE / 1:TRUE
0x0002 2 Bit0 = Alarm: Battery open 0:FALSE / 1:TRUE
0x0003 3
Bit15 = Alarm: IP N loss 0:FALSE / 1:TRUE
Bit14 = Alarm: IP site fail 0:FALSE / 1:TRUE
Bit13 = Alarm: Battery over charge 0:FALSE / 1:TRUE
Bit12 = Alarm: Overload warning 0:FALSE / 1:TRUE
Bit11 = Alarm: Fan lock warning 0:FALSE / 1:TRUE
Bit10 = Alarm: EPO active 0:FALSE / 1:TRUE
Bit8 = Alarm: Over temperature 0:FALSE / 1:TRUE
Bit6 = Alarm: Warning for maintain switch open 0:FALSE / 1:TRUE
Bit5 = Alarm: Redundancy warning 0:FALSE / 1:TRUE
Bit4 = Alarm: Utility extremely unbalanced 0:FALSE / 1:TRUE
Bit3 = Alarm: Bypass unstable 0:FALSE / 1:TRUE
Bit2 = Alarm: Battery High 0:FALSE / 1:TRUE
Bit1 = Alarm: Battery unbalance 0:FALSE / 1:TRUE
Bit0 = Alarm: Charger short 0:FALSE / 1:TRUE