63
6.OperationandCongurationofS3MUPSModels
and Battery Cabinets
6.2.3 Battery Setup
Click Battery Setup
6.2.4ConguringtheS3M10-20KUPSandOptimizingChargingofthe
BP240V09/BP240V09K, BP240V40 and BP240V40L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For
example, UPS model S3M20K3B has 60 internal batteries and is Battery Group 3. However, to connect a BP240V09
cabinet with 80 internal batteries to the S3M20K3B, the S3M20K3B UPS must be congured to a Battery Group 7 (seven
sets of 20 batteries). Obtain the Battery Group number based on the specic S3M UPS and Battery Cabinet models
combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to external battery cabinets
designed for the S3M-Series UPS Series.