5. Installation
5.3 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical
codes.
WARNING!
Typicalbatteryperformancedatareectsanoperatingtemperaturebetween59°Fto77°F(20°C
to25°C).OperatingtheUPSabovethisrangewillreducethebatterylife,whileoperatingtheUPS
below this range will reduce battery capacity.
5.3.1 Cable Sizes
Battery Cabinet
Models UPS Size
Recommended
DC Cable AWG
Recommended Ground
Cable AWG
Recommended
Cable Torque
BP240V09,
BP240V09K,
BP240V09-NIB
10kVA 6 AWG
Max 6 AWG
6 AWG
Max 2 AWG (35mm
2
)
Anderson Connector
(No Torque Parameter)
0kgf.com / 0N*m
15-20kVA 2 x 6 AWG
Max 6 AWG
2 x 6 AWG
Max 2 AWG (35mm
2
)
BP240V09,
BP240V09K,
BP240V09-NIB
25kVA 1/0 AWG 2 AWG 450kgf.cm/
44N•m
30kVA 1/0 AWG 1/0 AWG
BP240V40L,
BP240V40L-NIB
10kVA 6 AWG 6 AWG 450kgf.cm/
44N•m
15-20kVA 2 x 6 AWG 2 x 6 AWG
25kVA 1/0 AWG 2 AWG
30kVA 1/0 AWG 1/0 AWG
50kVA 2/0 AWG 2/0 AWG
5.4 Internal Battery Installation - Model BP240V09-NIB
The battery box includes built-in battery cables, breaker, fuses and terminals and can holds 80 units of 12V 9Ah
batteries, with output voltage of ±120V by battery connection. Four groups of batteries are connected in parallel for use,
and consist of BAT+, N, BAT-.
Figure 5-1: Models BP240V09 / BP240V09K / BP240V09-NIB
Loading ...
Loading ...
Loading ...