Installation of indoor unit
4. Wrap the indoor pipe and joint of
connection pipe with insulating pipe,
and then wrap it with tape.
Step 6: install drain hose
1. Connect the drain hose to the outlet pipe
of indoor unit.
2. Bind the joint with tape.
NOTE:
• Add insulating pipe in the indoor
drain hose in order to prevent condensation.
• The plastic expansion particles are
not provided.
Step 7: connect wire of indoor unit
1. Open the panel, remove the screw on
the wiring cover and then take down the cover.
Hex nut diameter Tightening torque (N.m)
ф 6 15~20
ф 9.52 30~40
ф 12 45~55
ф 16 60~65
ф 19 70~75
insulating pipe
drain hose
drain
hose
drain hose
insulating
pipe
panel
screw
wiring cover
outlet pipe
outlet
pipe
tape
open-end
wrench
union nut
pipe
indoor pipe
torque wrench