INSTALLATION
Side clearances - (Measurements B & C)
Where B, measured from the periphery of the nearest burner to any vertical combustible surface, or vertical
combustible surface covered with toughened glass or sheet metal, is less than 200mm, the surface shall be
protected to a height of C, of not less than 150mm above the hob for the full dimension (width or depth) of the
cooking surface area. Where the gas cooking appliance is tted with a ‘splashback’, protection of the rear wall is
not required.
Additional requirements for freestanding and elevated gas cooking appliances -
(Measurements D & E)
Where D, the distance from the periphery of the nearest burner to a horizontal combustible surface
is less than 200mm, then E shall be 10mm or more, or the horizontal surface shall be above the trivet.
Overheat clearances - (Measurement A)
The distance between the highest part of the hob of the gas cooking appliance should be
higher than 600mm for a range hood and higher than 750mm for an overhead exhaust fan.
6
00m
m
m
in 1
00m
m
m
in 6
00m
m
6
3
0
m
m
910mm
910mm
min 600mm
Anti-tilt bracket