90
5. CLI Commands
show region
Use the show region command to display the region information entered for the sensor.
Syntax
show region
Examples
The following command displays the region information entered for sensor “Temp1”, associated with device “PDU123”:
console> device (PDU123)> sensor (Temp1)> show region
Chicago
device: sensor: show
show
Use the show command, with optional keywords, to display details about the sensor. To view all keywords applicable to the
sensor, enter show [Tab][Tab].
Syntax
show [keyword-1 [keyword-2 [keyword-3 [keyword-4 [keyword-5 [keyword-6]]]]]]
keyword-x – Specifies the attribute(s) to be displayed. Up to 6 keywords can be used per command.
Examples
The following command displays all show keywords for sensor “TopCombo”, associated with device “PDU123”:
console> device (PDU123)> sensor (TopCombo)> show [Tab][Tab]
alarm-level description location region
asset-tag details low-critical serial-number
contact help manufacturer supported
contact-1 high-critical model temperature
contact-2 humidity name threshold
count id output tolerance
date-installed input protocol
The following command displays all details for sensor “TopCombo”, associated with device “PDU123”:
console> device (PDU123)> sensor (TopCombo)> show
Name : TopCombo
Active : yes
Type : EnviroSense
Manufacturer : TRUPP LITE
Model : E2MTHDI
Serial # : 2631AV0AC886D00014
Install Date : 3/2/2020
Protocol : 9300
Device ID : 0
Asset Tag :
Region :
Location :