5. CLI Commands
device: id
id
Use the id command to optionally set a numeric identifier for the device. Use the no form of this command to clear the entry.
Syntax
id <id>
id – Specifies a numerical identifier for the device (Range: 0-65535).
Example
The following command sets “98765” as the numerical identifier for device “PDU-Rack1”:
console> device (PDU-Rack1)> id 98765
Update complete
show id
Use the show id command to display the identifier entered for the device.
Syntax
show id
Examples
The following command displays the numerical identifier for device “PDU-Rack1”:
console> device (PDU-Rack1)> show id
98765
device: input
input
Use the input command to configure the device’s input settings. Input parameters vary by device type and model; use
keywords to identify applicable input parameters. Use the force option to execute the input voltage reset command without
confirmation.
Syntax
input voltage reset [force]
input voltage {l1-l2 | l2-l3 | l3-l1} reset [force]
input voltage threshold {low-critical | low-warning | high-warning | high-critical} <decimal-value>
input voltage {l1-l2 | l2-l3 | l3-l1} threshold {low-critical | low-warning | high-warning | high-critical} <decimal-
value>
input voltage threshold {high-transfer | low-transfer} <decimal-value>
input {high-warning | low-warning} threshold voltage <decimal-value>
input voltage threshold tolerance <decimal-value>
decimal-value – Specifies the numerical value for the threshold or tolerance.