66
FlexFit Pro
AM24LP2VHA
PCB 0151800267
SW3-5 SW3-6 SW3-7 SW3-8
Indoor unit Address
(Indoor unit address for one wired
controller control more than one
unit)
OFF OFF OFF OFF 0 (master)
OFF OFF OFF ON 1(slave)
OFF OFF ON OFF 2(slave)
OFF OFF ON ON 3(slave)
OFF ON OFF OFF 4(slave)
OFF ON OFF ON 5(slave)
OFF ON ON OFF 6(slave)
OFF ON ON ON 7(slave)
ON OFF OFF OFF 8(slave)
ON OFF OFF ON 9(slave)
ON OFF ON OFF 10(slave)
ON OFF ON ON 11(slave)
ON ON OFF OFF 12(slave)
ON ON OFF ON 13(slave)
ON ON ON OFF 14(slave)
ON ON ON ON 15(slave)
Wired controller communication address
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
1 1 0 --- --- --- --- --- AM24LP2VHA
--- --- --- 0 --- --- --- --- Room card invalid(default)
--- --- --- 1 --- --- --- --- Room card valid
--- --- --- --- 0 --- --- --- Cool and heat(default)
--- --- --- --- 1 --- --- --- Cool only
--- --- --- --- --- 0 --- --- External alarm output(default)
--- --- --- --- --- 1 --- --- Fresh air
--- --- --- --- --- --- 0 --- Without lter clean remind (default)
--- --- --- --- --- --- 1 --- With lter clean remind
--- --- --- --- --- --- --- 0 ESP DUCT ( USA)
--- --- --- --- --- --- --- 1 EU. &Australia