50
FlexFit Pro
1. Specications
Item Model 1U24LP2VHA
Power cable H05RN-F 3G 4.0mm
2
Communication cable/Connecting cable H05RN-F 4G 2.5mm
2
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Start current A 3
Outdoor
unit
Unit model (color) 1U24LP2VHA (WHITE)
Compressor
Model/Manufacture/
place
TNB220FFEMC
Oil model FV50S
Oil charging CC 520
Type Rotary
Fan
Type×Number Axial×1
Speed r/min 650/600/500/400/300/200
Fan motor output/input
power
kW 100/120
Air-ow (H-M-L) m
3
/h 3200
Coil
Type/Diameter mm TP2M/Φ7 wide n
Row/Fin pitch 2 1.65
Total area m
2
/
Dimensions
External (L×M×H) mm×mm×mm 965*950*370
Package (L×M×H) mm×mm×mm 1095*1050*450
Drainage pipe (material, I.D./O.D.) mm None
Refrigerant control method mm/mm 2.2mm electronic expansion valve
Defrosting Auto
Volume of accumulator L 2.1
Sound power noise level (H-M-L) dB (A) 64
Sound pressure noise level (H-M-L) dB (A) 47
Type of four way valve SHF-4-10A
Insulation material Felt
Crankcase heater power W /
Weight (Net/Shipping) kg/kg 80/92
Piping
Refrigerant
Type/Charge g R410A/2500
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Connecting method Flared
Between I.D &O.D
MAX. Drop m 30
MAX. Piping length m 50
Maximum pipe length
without recharge
refrigerant
m 20
Working
temp.
Cooling (Min-Max) °C -15~50
Heating (Min-Max) °C -20~24
Norminal condition:
Indoor temperature (cooling) : 80.6DB (°F)/66WB (°C) , Indoor temperature (heating) : 68DB (°F)
Outdoor temperature (cooling) : 95DB (°F)/75WB (°F) , Outdoor temperature (heating) : 44.6DB (°F)/42.8WB (°F)
The noise level will be measured in the third octave band limited values, using a Real Time Analyzer calibrated
sound intensity meter. It is a sound pressure noise level.