NOTE: At any time during wireless alarm setup, if you have a problem, you can push and hold the Test/Hush
button on any problem unit until you hear three (3) beeps (approx 8 sec), and then release the button. The unit will
reset the unit’s wireless settings (described in Section 9.3). Once wireless settings are reset, the unit will prompt the
user to follow Quickstart instructions.
NOTE: Wireless units will emit a series of LED blinks, tones, and voices as the unit(s) search for a wireless alarm setup.
If you are intending to use wireless units without the wireless function, ignore these notifications, and the wireless
function will eventually turn off. You can turn the wireless function on again at a later date if desired. See Section 9.2.
NOTE: The battery activation is a one-time feature. After activation, the battery cannot be turned off, and can only
be discharged at the end of product life. If the alarm is removed from the mounting plate, the battery will remain
active. See Permanently Disable Alarm / Discharge Battery section.
Wireless
These models have wireless alarm interconnect
capability. When one interconnected unit sounds
an alarm, all other compatible wireless units in
the wireless alarm network will alarm.
A maximum of 24 Kidde Safety devices may be interconnected in a multiple station arrangement. The intercon-
nect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, CO,
Smoke/ CO Combination, heat, etc.). With 18 alarms interconnected, it is still possible to interconnect up to a total of
6 remote signaling devices and / or relay modules.
Maximum distance between wireless interconnect models is greater than 300 feet in open air.
COMPATIBLE WIRELESS INTERCONNECT UNITS
AC Models: P4010ACSCO-W, P4010LACS-W, P4010ACS-W
DC Models: P4010LDCS-W, P4010DCS-W, P4010DCSCO-W