Weil-McLain ULTRA S4 GAS BOILER UG-230 Ultra S4 Gas Boiler Ug80 Ultra S4 Residential Gas Water Boiler

User Manual - Page 119

For ULTRA S4 GAS BOILER UG-230.

PDF File Manual, 140 pages, Read Online | Download pdf file

ULTRA S4 GAS BOILER UG-230 photo
Loading ...
Loading ...
Loading ...
Part number 550-100-400/0119
119
฀฀
Troubleshooting (continued)
Display
Condition Diagnostics Corrective Action(s)
Nothing
is shown
in display
screen and no
other boiler
components are
operating
Control is not receiving 120V
power.
Check service switch and/or
circuit breaker to boiler turned
is on.
Turn on service switch to power boiler.
Is there 120 Volts at the service
switch?
Troubleshoot and correct the power supply to the service switch.
Is the Ultra's ON/OFF POWER
SWITCH located behind the
control pod turned on?
Turn the Ultra's power switch behind the control pod to ON.
Check for 120 volts at the line
voltage terminal block located
inside the control pod.
Correct wiring inside the control pod using the wiring diagram in this
manual.
Inspect 12-amp fuse as shown
on page 100. Replace if
necessary.
Replace the fuse with proper part found in the replacement part section
of this manual. If fuse blows again recheck wiring per diagram.
Nothing is
shown on
display screen,
but boiler is
operating
Occurs when the
communication is lost from
the U-control to the display.
Check for loose connections
and proper pin alignment/
engagement on the U-Control's
plug P9 and the back of the
display circuit board.
Check for continuity on the wire harness from the display to the
U-control. See repair parts section for proper replacement part.
Cycle power off and on using
boiler power switch and check
for operation.
Replace with new display module. See repair parts section for proper
replacement part.
5&.13*4&500
QUICKLY
Occurs when supply
water temperature in heat
exchanger rises faster than
2ºF per second during the
rst two minutes the burner
is on.
Automatically resets after 1
minute delay or using manual
reset on display.
Manual reset is necessary after 5
automatic resets have occurred
during the same Priority heat
demand. Reset using manual
reset screen on display.
Verify water pipe is installed correctly using primary/secondary
connection to the boiler loop. Refer to Figure 4 page 11 for example of
primary/secondary connection.
Minimum pipe sizes
Ultra 80/105 - minimum 1 inch
Ultra 155/230 - minimum 1.25 inch
Ultra 299/310/399 - minimum 1.5 inch
Verify proper circulator sizing for boiler size and system requirements
starting on page 9.
Boiler ship with proper size circulators:
Ultra 80/105 - Taco 007e ECM
Ultra 155/230/299/310 - Taco 0014
Ultra 399 - Taco 0013
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
4611-:'
3&563/
Boiler Out temperature
has exceeded the Boiler In
temperature by more than
58ºF, when burner is on.
Automatically resets after 30
second delay or using manual
reset on display.
Verify water pipe is installed correctly using primary/secondary
connection to the boiler loop. Refer to Figure 4 page 11 for example of
primary/secondary connection.
Minimum pipe sizes
Ultra 80/105 - minimum 1 inch
Ultra 155/230 - minimum 1.25 inch
Ultra 299/310/399 - minimum 1.5 inch
Verify proper circulator sizing for boiler size and system requirements
starting on page 9.
Boiler ship with proper size circulators:
Ultra 80/105 -Taco 007e ECM
Ultra 155/230/299/310 - Taco 0014
Ultra 399 - Taco 0013
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
iure  Trouleshootin suestions for Ultra oilers (continued)
®
Series 4
gas-fired water boiler — Boiler Manual
Loading ...
Loading ...
Loading ...