Loading ...
Loading ...
Loading ...
CAUTION
• Install the indoor unit leveled.
If the indoor unit is inclined and the drain piping side gets
high,itmaycausemalfunctionofoatswitchandresultin
water leakage.
• Attach nuts on the upper and lower side of hanger.
If there is no upper nut and the lower nut is over-tightened,
the hanger and the top plate will deform and cause abnormal
sound.
• Donotinsertmaterialsotherthanthatspeciedinto
the clearance between the hanger and the washer for
hanger bracket (11).
Unless the washers are properly attached, the
suspension bolts may come off from the hanger.
WARNING
The indoor unit must be securely installed on a place
that can withstand the mass.
Ifthestrengthisinsufcient,theindoorunitmayfalldown
and cause injuries.
6. REFRIGERANT PIPING WORK
Refer to the installation manual for the outdoor unit also.
• Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
temperature is not less than 230°F (110°C).
For use under high humidity, strengthen the insulation
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat.
(1) Flaring the pipe end
1. Cut the pipe end with a pipe cutter.
2. Remove burrs with the cut surface facing downward,
sothatthelingsdonotenterthepipe.
3.Putthearenutonthepipe.
4. Flare the pipe.
5.Checkthatthearinghasbeendonecorrectly.
Theare’sinnersurface
mustbeaw-free.
Thepipeendmust
beevenlyaredina
perfectcircle.
Makesurethatthe
arenutistted.
Check
A
Cutexactlyatrightangles. Removeburrs
Setexactlyatthepositionshownbelow.
A
0-0.02in
(0-0.5mm)
0.04-0.06in
(1.0-1.5mm)
0.06-0.08in
(1.5-2.0mm)
Clutch-type
FlaretoolforR410A
Clutch-type
(Rigid-type)
Wing-nuttype
(Imperial-type)
Conventionalaretool
Flaring
Die
WARNING
• Donotapplymineraloiltotheare.
• Prevent mineral oil from getting into the system as
this would reduce the service life of the units.
•
Never use piping which has been used for previous
installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R410A unit in order to
guarantee its service life.
•
The drying material may dissolve and damage the system.
•
Incompletearingmayresultinrefrigerantgasleakage.
CAUTION
• Usethearenutxedtothemainunit.(Thisisto
preventthearenutfromcrackingasaresultof
deterioration over time.)
• Useapipecutterandaresuitableforthetypeof
refrigerant.
• To prevent gas leakage, apply refrigeration oil only to
theinnersurfaceoftheare.(Userefrigerationoilfor
R410A.) (Refer to Fig. 10)
• Useatorquewrenchwhentighteningthearenutsto
preventdamagetothearenutsandgasleakage.
•
Protect the open end of the pipe against dust and moisture.
•
Do not allow anything other than the designated
refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on
the unit, ventilate the room thoroughly right away.
•
Useonlythearenutsattachedtotheairconditioner.If
otherarenutsareused,itmaycauserefrigerantleakage.
(2) Refrigerant piping
1. To prevent gas leakage, apply refrigeration machine
oilonlytotheinnersurfaceoftheare.(Use
refrigeration oil for R410A)
2.Alignthecentersofbotharesandtightentheare
nuts 3 or 4 turns by hand, then tighten them fully with
a spanner and a torque wrench.
• Useatorquewrenchwhentighteningthearenuts
topreventdamagetothearenutsandgasleakage.
(Refer to Fig. 9)
Flare nut tightening torque
Gas side Liquid side
3/8 inch
(9.5mm)
1/2 inch
(12.7mm)
5/8 inch
(15.9mm)
1/4 inch
(6.4mm)
24.1-29.4ft•lbf
(32.7-39.9N•m)
36.5-44.5ft•lbf
(49.5-60.3Nm)
45.6-55.6ft•lbf
(61.8-75.4N•m)
10.4-12.7ftlbf
(14.2-17.2N•m)
7 English
Loading ...
Loading ...
Loading ...