1) Set to COOL or HEAT operation using the remote
controller.
2) PressandholdCancelbuttonfor4secondsorlonger.
Service settings menu is displayed.
3) Select
Test Operation in the service settings menu, and
press Menu/OK button. Basic screen returns and “Test
Operation” is displayed at the bottom.
4) PressOn/Offbuttonwithin10seconds,andthetest
operation starts.
Monitor the operation of the indoor unit for a minimum
of 10 minutes. During test operation, the indoor unit
will continue to cool/heat regardless of the temperature
setpoint and room temperature.
• In the case of above-mentioned procedures 3) and 4)
in reverse order, test operation can start as well.
5) PressandholdCancelbuttonfor4secondsorlongerin
the basic screen.
Service settings menu is displayed.
6) Select
Test Operation in the service settings menu, and
press Menu/OK button. Basic screen returns and normal
operation is conducted.
• Test operation will stop automatically after 15-30
minutes. To stop the operation, press On/Off button.
Basic screen
1)
2)
Cool
Return Cleanthelter
Set to
Cool
68F
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Service Settings
menu screen
3)
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Press Menu/OK button.
4)
Set temperature
80°F
Cool
Test Operation
Press On/Off button
(within 10 seconds).
5)
Set temperature
80°F
Cool
Test Operation
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
6)
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Press Menu/OK button.
Basic screen
English 16