The drain pipe installation for the unit with pump.
The drain pipe installation for the unit without pump.
Lean over 1/50
Fig.11-1
Fig.11-2
Lean over 1/50
Drainage testDrainage test
Check whether the drainpipe is unhindered.
New built house should have this test done before paving
the ceiling.
The unit with pump.
Remove the test cover, and stow about 2000ml water to the
water pan.
1
NOTE
Fig.11-5
Install the drain joint of the outdoor unit
(For Heat Pump Models)
Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of outdoor, rotate 90° to securely assemble them.
Connect the drain joint with an extension drain hose (Locally
purchased)to avoid condensate draining off the outdoor unit
during the heating mode.
Seal
Base pan hole
Drain joint
Seal
Base pan
Drain
joint
Fig.11-6
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you
purchased.The actual unit shall prevail.
The unit without pump.
Stow 2000ml water to the water pan through the stow
tube,check whether the drainpipe is unhindered.
Stow tube
Fig.12-1
12. FRESH AIR DUCT INSTALLATION
Dimension :
Duct joint for fresh air
3.15in/80mm
3.15in/80mm
Ø90mm/3.54in
Ø125mm/4.92in
Ø160mm/6.3in
MODLE
12-24 30-60
Operate the air conditioner in "COOLING" mode. The sound of
the drain pump shall be heard. Check whether the water is
discharged well (1 min lag is possible, according to the length of
the drain pipe), and check whether the water leaks from the
joints.
2
Power off the air conditioner and recover the cap.
3
Test cap
Fig.11-3
Fig.11-4
C
L
O
S
E
D
O
P
E
N
C
L
O
S
E
D
O
P
E
N
Stow tube
19
installation manual
3.28-4.92ft/1-1.5m
7.87in/200mm
21.65in/550mm
3.28-4.92ft/1-1.5m
For more details visit www.mrcool.com