Installation Manual 89
Group Number setting for Indoor Units
Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
The communication lines connected to INTERNET terminal should be connected to central control of
Outdoor unit with care for their polarity( A
A, B
B )
Turn the whole system on.
Set the group and Indoor Unit number with a wired remote control.
To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
B(D) A(C) B A
SODU B SODU A IDU IDU INT B INT A
Outdoor Units
Terminal block on the main PCB
Group recognizing the simple central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
WARNING
Valve (04)
EX)
Valve (03)
Valve (02)
Valve (01)
Indoor unit (04)
Indoor unit (03)
Indoor unit (02)
Indoor unit (01)
Central control address
HR unit
• Valve address and central control address of its corresponding indoor unit should be set identical in
manual addressing.
Group Number Setting
HR Unit PCB
Loading ...