Installation Manual 39
Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
Pipe connection between outdoor units
(General Case)
Pipes between outdoor units are
2m(6.6ft) or less
Pipes between outdoor units are
2m(6.6ft) or longer
The maximum pipe length
after the first branching
between the outdoor units is
10m(33ft) or less
2m(6.6ft) or less
Oil Trap
Oil Trap Oil Trap
2m(6.6ft) or less
2m(6.6ft) or less
2m(6.6ft) or less
0.2m(0.66ft)
or more
2m(6.6ft) or longer
2m(6.6ft) or longer2m(6.6ft) or longer
Examples of Wrong Pipe Connections
If the distance between the outdoor units becomes more than 2m(6.6ft), apply Oil Traps between the gas pipes.
If the outdoor unit is located lower than the main pipe, apply Oil Trap.
If the main pipe is higher
than the outdoor units, oil
is accumulated in the
outdoor unit.
If there are differences in the height
between the outdoor units, oil is
accumulated in the lower outdoor unit.
Oil Trap
Refrigerant piping system