LG Electronics ARUB096BT3

User Manual - Page 54

For ARUB096BT3.

PDF File Manual, 117 pages, Download pdf file

Loading ...
Loading ...
Loading ...
54 Outdoor Unit
Electrical Wiring
Caution
Electrical Wiring
Remote
control
Remote
control
Remote
control
Remote
control
Indoor
Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
CAUTION
Be sure to connect the outdoor unit to earth. Do not connect earth line to any gas pipe, liquid pipe,
lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
CAUTION
Be sure to have authorized electrical engineers do the electric work using special circuits in
accordance with regulations and this installation manual. If power supply circuit has a lack of
capacity or electric work deficiency, it may cause an electric shock or fire.
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
2. Install the Outdoor Unit communication line away from the power source wiring so that it is not affected by
electric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to Outdoor Unit.
4. Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is sometimes
removed at the time of service work.
5. Never connect the main power source to terminal block of communication line. If connected, electrical parts will be
burnt out.
6. Use 2-core shield cable for communication line.(O mark in the figure below) If communication lines of different
systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause
erroneous operations. ( mark in the figure below)
7. Only the communication line specified should be connected to the terminal block for Outdoor Unit communication.
2-Core Shield Cable Multi-Core Cable
Loading ...
Loading ...
Loading ...