66 Outdoor Unit
Electrical Wiring
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Between Indoor and Master Outdoor unit
Master
Outdoor Unit
SODU B SODU A IDU IDU INT B INT A
Master
Outdoor Unit
SODU B SODU A IDU IDU INT B INT A
Slave
Outdoor Unit
SODU B SODU A IDU IDU INT B INT A
HR unit
A B
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.