User manual Generator
-890423.png)
Proper tools, equipment, and qualified personnel must be used in all phases of handling and moving the generator. The approximate weight of the generator appears in the Generator Specifications section.
Use the lifting holes (A) in the base of the generator to lift the generator onto the concrete pad. Lift the generator in accordance with the Occupational Safety and Health Administration (OSHA) or local lifting regulations. Retouch any chipped paint with the supplied touch-up paint.
-267729.png)
If the generator operates in temperatures below 30° F (-1° C), Briggs & Stratton highly recommends that the installer install a cold weather kit.
Oil Sump Warmer Kit, Part Number 6840-00, includes:
Fuel Regulator Warmer Kit, Part Number 6845-00, includes:
Battery Warmer Kit, Part Number 6869-00, includes:
Find these items at the local service dealer.
For more information, please call 800-732-2989 between 8:00 a.m. and 5:00 p.m. CT.
-224596.png)
Concrete Anchoring of Unit to Poured or Existing Slab
To achieve the listed wind rating, the generator must be installed in strict compliance with this Installation and Operation Manual. The product components must be of the material specified and all screws must be installed in accordance with the applicable provisions and the anchor manufacturer’s published installation instructions.
The concrete slab or pad must meet the requirements below and the generator must be anchored with one of the following anchor types.
There are four 7/16-inch hole locations (A) in the base of the generator in which to anchor the unit.
-172933.png)
-30624.png)
Find these items at the local service dealer.
Note
Unless mandated by local or state codes, or required to achieve wind rating, a concrete slab or pad is not required.
The 3/4-inch N.P.T. fuel inlet connector (A) and electrical inlet locations (B) are shown in Figure 7.
A 1.73 inch (44 mm) knock-out hole is provided for the electrical inlet. Make sure that the installed conduit(s) enter the unit in zone (C) as shown in the drawing below so that they properly enter the electrical box and do not interfere with the fully opened roof.
-765721.png)
The generator enclosure has several access panels, as shown.
The access panels and the components located behind them are listed below:
(A) Roof (Controller, air filter, oil dipstick, and circuit breaker)
(B) Front Access Panel (oil drain, oil filter, battery)
(C) End Cap, Controller End (control box wiring cover, fuel regulator, fuel selector, generator data label)
(D) End Cap, Exhaust End (alternator fan)
(E) Rear Access Panel (engine starter, starter relay)
(F) Control Box Wiring Cover (field wiring, control wiring)
Each generator ships with a set of identical keys fastened to the fuel solenoid.
-920002.png)
Opening the roof (A):
Removing the front panel (B):
Attaching the front panel (B):
Removing the end cap, controller end (C):
Attaching the end cap (C):
Removing the end cap, exhaust end (D):
Attaching the end cap, exhaust end (D):
Removing the rear panel (E):
Attaching the rear panel (E):
Removing the control box wiring cover (F):
Attaching the control box wiring cover (F):
WARNING Propane and natural gas are extremely flammable and explosive, which could cause burns, fire, or explosion, resulting in death or serious injury.
NOTE
DO NOT install the supplied flexible fuel line underground or in contact with the ground.
The following information addresses the planning phase of installations for technicians specializing in gaseous fuel systems. Always obey the local applicable fuel-gas codes affecting the installation site. Consult your local fuel supplier or fire marshal with any questions or problems.
TO THE INSTALLER: Consult with the generator owner(s) and address any technical considerations affecting their installation plans before applying these guidelines.
The following general rules apply to piping on gaseous fuel systems:
NOTE Keep thread sealant out of the gas piping to prevent damage to component parts.
-499947.png)
(A) Generator Fuel Inlet
(B) Flexible Fuel Line
(C) Union Fitting
(D) Manometer Test Port
(E) Sediment Trap
(F) Manual Shut-off Valve
The following chart shows estimated fuel supply requirements at half and full load for natural gas and liquefied petroleum vapor fuels.
-792654.png)
-125018.png)
-16856.png)
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water during combustion.
*** Density is given in “Cubic Feet of Gas per Gallon of Liquid.”
† Weight is given in “Pounds per Gallon of Liquid.”
Consider the type of fuel that your generator uses, as it affects the entire installation process. The system was factory tested and adjusted using natural gas, but it can be converted to use liquefied petroleum vapor. For correct engine function, consider factors that affect each of these fuels, such as the location and the duration of possible utility interruptions. Follow these guidelines when choosing fuel type:
Natural gas or LP engines are certified to operate on natural or liquid propane gas. The emissions control system for this engine is EM (Engine Modifications).
Both LP vapor and natural gas fuel supply pressure at the generator’s fuel inlet port must be a minimum value at full load with all gas appliances turned on and in operation.
Natural Gas must be 3.5-7 inches Water Column (WC).
Liquefied Petroleum must be 11-14 inches WC.
Ensure that all gas line shut-off valves are OPEN and that adequate fuel pressure is available whenever automatic operation is needed.
WARNING Failure to read and obey the operator’s manual, all warnings, and operating instructions could result in death or serious injury.
Front View
-953480.png)
for clarity. Legend for System Connector Locations:
(A) Lifting Holes — Provided at each corner for lifting generator
(B) Muffler — High-performance muffler lowers engine noise to comply with most residential codes
(C) Circuit Breaker — Protects the system from shorts and other over-current conditions
(D) Controller — Facilitates for generator operation control, menu start-up, and informational display functions
(E) Air Cleaner — Uses a dry-type filter element to protect engine by filtering dust and debris out of intake air
(F) Engine Label — Identifies engine model and type (located on the valve cover)
(G) Spark Plug — A device in the cylinder head of the engine that ignites the fuel mixture by means of an electric spark
(H) Oil Filter — Filters engine oil to prolong generator life
(J) Battery (installer supplied) — 12VDC, lead acid, automotive-style battery provides power to start the engine
(K) Oil Drain Hose — Facilitates oil changing
Back View
-414515.png)
(A) Lifting Holes — Provided at each corner for lifting generator
(B) Fuel Solenoid — Automatically opens and closes to supply fuel to the unit when needed
(C) Fuel Regulator — Controls fuel flow to the engine for proper operation
(D) Fuel Selector Valve (not shown) — Aids in selecting the proper fuel type (LP or NG)
(E) Spark Plug — A device in the cylinder head of the engine that ignites the fuel mixture by means of an electric spark
(F) ON/OFF Switch — Aids in turning the generator on (I) and off (0)
(G) Oil Fill Cap — The location for adding oil to the engine
(H) Electrical Field Wiring Inlet — Wires to and from the generator are centered in this location
(J) Air Cleaner — Uses a dry-type filter element to protect the engine by filtering dust and debris out of the intake air
(K) Engine Oil Dipstick — Allows the user to check the engine oil level easily
(L) Alternator — An electrical machine that generates an alternating current
-537473.png)
(A) Fuse Holder — For the 15-amp ATO-type fuse (fuse holder is located below the controller)
(B) Generator Data Label — Identifies the generator model number and serial number. Located inside the battery access compartment
-607146.png)
(A) Status LED — Three modes:
WARNING Engine exhaust contains carbon monoxide, a poisonous gas that could kill people and animals in minutes. People and animals cannot smell it, see it, or taste it. Even if you do not smell exhaust fumes, you could still be exposed to carbon monoxide gas.
WARNING Propane and natural gas are extremely flammable and explosive, which could cause burns, fire, or explosion, resulting in death or serious injury.
The engines ships from the factory pre-run and filled with full synthetic oil (API SJ/CF 5W-30). This step allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check the oil level as described in the Maintenance section.
NOTE Any attempt to crank or start the engine before it has been correctly filled with the recommended oil will result in equipment failure.
The installer must supply a rechargeable 12VDC starting battery. See Battery in the Final Considerations section.
Ensure that the fuse is correctly installed before operating the generator.
The generator’s controller monitors utility voltage. If the utility voltage drops below a preset level, the controller signals the engine to crank and start. When the utility voltage restores above a preset voltage level, the engine receives signals to shut down. The actual system operation is not adjustable and undergoes sequencing by sensors and timers on the controller in the following manner:
This sensor monitors the utility voltage. When the utility voltage restores above approximately 80% of the nominal source voltage, a shut-down timer initiates and the engine cools down.
When the system senses the utility power, the load transfers to the utility source and the engine enters a fiveminute cool-down period.
-188710.png)
A detailed list of all the on-screen parameters appears in the Configuration of GCU section inside the online Operation Instructions GC1030 SERIES GENSET Controller Manual (part number 80086364).
WARNING Generator voltage could cause electrical shock or burns, resulting in death or serious injury.
WARNING With the battery connected, the generator may crank and start without warning, resulting in death or serious injury.
Always follow these steps before performing any generator maintenance:
Follow the hourly or calendar intervals of operation, whichever occurs first.
Every 8 Hours of Operation or Daily
Clean Debris
Check the Engine Oil Level
Every 100 Hours of Operation or Annually
Change the Air Filter
Change the Engine Oil and Filter
Replace the Spark Plugs
Check the Valve Clearance
Check the Circuit Breaker Torques
Annually
Clean the Oil Cooler Fins
Regular maintenance improves the performance and extends the life of the generator. See any authorized dealer for service.
Any individual, whether from a non-road engine repair establishment or not, can perform maintenance, replacement, or repair of the emissions control devices and systems. However, only a factory-authorized dealer must do the work required to obtain a “no charge” emissions control service. See the Emissions Warranty for details.
The generator’s warranty does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
The generator requires the owner to make some adjustments periodically to correctly maintain it.
Perform all service and adjustments at least once each season. Obey the requirements in the Maintenance Schedule section.
Generator maintenance also means keeping the unit clean. Operate the unit in an environment that remains free of excessive dust, dirt, moisture, or any corrosive vapors. Do not allow the cooling air inlets and outlets on the enclosure to become clogged with snow, leaves, or other foreign material. To prevent generator damage caused by overheating, keep the enclosure cooling inlets and outlets clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean it when dust, dirt, oil, moisture, or other foreign substances appear on its exterior and interior surface. Inspect the air inlet and outlet openings inside and outside the enclosure to make sure no blockages exist in the airflow.
NOTE Improperly treating the generator can damage it and shorten its life.
WARNING Exhaust heat/gases could ignite combustibles, causing a fire and resulting in death or serious injury.
NOTE
Engine Oil
Use only Briggs & Stratton® 80028446 SAE 5W-30 full synthetic engine oil. Other full synthetic high-quality detergent oils are acceptable if classified for service SJ or higher. Do not use special additives.
Checking the Engine Oil Level
Maintain the oil level somewhere between the “add” and the “full” marks on the dipstick. Before checking the oil level, follow these steps to ensure that an accurate reading appears on the dipstick:
-5735.png)
See the Alarms section of the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details on service alarm description and causes.
| PROBLEM | CAUSE | CORRECTION |
| The engine is running, but no AC output is available. |
1. Open or defective circuit breaker 2. An alarm on the generator’s controller 3. Poor wiring connections or defective transfer switch |
1. Reset or replace the circuit breaker. 2. See the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details. Contact the local service facility. 3. Check and repair it or contact the local service facility. |
| The engine runs well at no-load but “bogs down” when loads are connected. |
1. Overloaded generator 2. Short circuit in a connected load 3. Shorted generator circuit 4. Incorrect fuel pressure or mixture 5. Kinked fuel line between the regulator and engine 6. Clogged air filter |
1. Remove one or more loads. 2. Disconnect the shorted electrical load. 3. Contact the local service facility. 4. See The Gaseous Fuel System section. 5. Remove the kink. Replace the line if necessary. 6. Clean or replace the air filter |
| The engine does not start or it starts but runs rough. |
1. Missing or blown 15-amp fuse 2. Blown thermal fuse(s). 3. Fuel supply turned off or depleted 4. Incorrect fuel selection 5. Failed battery 6. Clogged air filter 7. Throttle linkage binding |
1. Install a new 15-amp fuse. See the System Controller section. Replace the thermal fuse(s). 2. Replace the thermal fuse(s). 3. Open the fuel valve(s} and check the propane tank. 4. Check the fuel selector switch and set it to the proper setting (if applicable). 5. Replace the battery. 6. Clean or replace the air filter. 7. Check the linkage. |
| The engine shuts down during operation. |
1. Fuel supply turned off or depleted 2. Alarm showing on the controller digital display |
1. Check the fuel valves and fill the propane tank. 2. See the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details. |
| The circuits lose power. |
1. An open generator circuit breaker 2. Transfer switch problems |
1. Reset the circuit breaker. 2. See the transfer switch manual. |
| The unit does not exercise. |
1. Controller not set to auto. 2. Exercise timer not set or set to OFF. 3. Unit date and time not set. 4. Failed battery. 5. Missing or blown 15-amp fuse. |
1. Push the auto button on the controller. 2. Set the exercise timer. 3. Set the unit date and time. 4. Replace the battery. 5. Install a new 15-amp fuse. See the System Controller section. |
| The generator undergoes excessive vibration | . Loose mechanical fastener. | Check and repair it or contact the local service facility. |
| Utility power returns and the unit does not stop. |
1. Blown fuses in the transfer switch. 2. The five-minute cooldown still in process. 3. Poor wire connection or defective controllers. |
1. Install new fuses. 2. Wait five minutes. 3. Check and repair the unit or contact the local service facility. |
| Possible issues exist in manual mode. | – | See Table 7 (Common Faults and Their Remedial Actions) inside the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details. |
| Possible issues exist in auto mode. | – | See Table 7 (Common Faults and Their Remedial Actions) inside the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details. |
| Possible issues exist with Electronic Governing. | – | See Table 7 (Common Faults and Their Remedial Actions) inside the separate online manual titled Operation Instructions GC1030 SERIES GENSET Controller (part number 80086364) for details. |
Call 800-732-2989 or visit www.briggsandstratton.com for assistance.