MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
INSTALLING MULTI F SYSTEMS
Connection sockets (included as a factory-supplied accessory with the
indoor units) will need to be used when piping the indoor units to the out-
door unit. See tables above and below for indoor unit piping connection
and connection socket dimensions. If a 36K indoor unit is included, the
connection sockets are included with the Branch Distribution unit.
Table 20: Outdoor Unit Piping Connections.
Figure 43: Multi F Refrigerant Pipe Connections
(LMU36CHV shown as example).
Avoid Pipe Damage
When routing field-provided piping, avoid damaging the outdoor unit from excessive
vibration.
Properly insulate the liquid and gas lines separately up to the point of connection at the
unit frame.
See table below for Multi F outdoor unit connection types.
Main gas
valve
Main liquid
valve
Gas Piping Connections
Liquid
Piping
Connections
A-UNIT
B-UNIT
C-UNIT
D-UNIT
Indoor Unit Capacity
Vapor (in., OD)
Liquid (in.,
OD)
A B A B
18,000 Btu/h: Wall-Mounted
ĺĺ
Ø5/8
ĺ
15,000 Btu/h: Console;
18,000 Btu/h: Low Static
Duct, Four-Way Cassette
ĺ N/A
24,000 Btu/h ĺ N/A
Multi F Outdoor Unit to Indoor Unit Piping Connections
Outdoor Unit Piping Connections LMU18CHV LMU24CHV LMU30CHV LMU36CHV
Liquid Line Connection (in., OD) x Qty. 1/4 x 2 1/4 x 3 1/4 x 4 1/4 x 4
Vapor Line Connection (in., OD) x Qty. 3/8 x 2 3/8 x 3 3/8 x 4 3/8 x 4
Table 21: Indoor Unit Pipe Sizes.
Indoor Unit Capacity
Vapor Line
Piping Size (in., OD)
Liquid Line
Piping Size (in., OD)
7,000 Btu/h
Ø3/8
Ø1/4
9,000 Btu/h
12,000 Btu/h
15,000 Btu/h
15,000 Btu/h: Console;
18,000 Btu/h
Ø1/2
24,000 Btu/h
Table 22: Indoor Unit Piping Connections.
Indoor Unit Capacity
Vapor Line
Conn. (in., OD)
Liquid Line
Conn. (in., OD)
7,000 Btu/h
Ø3/8 Ø1/4
9,000 Btu/h
12,000 Btu/h
15,000 Btu/h
18,000 Btu/h: Wall-Mounted Ø5/8 Ø3/8
15,000 Btu/h: Console;
18,000 Btu/h: Low Static Duct,
Four-Way Cassette
Ø1/2 Ø1/4
24,000 Btu/h Ø1/2 Ø1/4
Correctly route the piping so it does not make contact with mounting bolts. Allow room
IRU¿HOGLQVWDOODWLRQ
Table 23: Connection Socket Dimensions.