Carrier FX4BNF018000AAAA fan coil

User Manual - Page 16

For FX4BNF018000AAAA.

PDF File Manual, 16 pages, Download pdf file

Loading ...
Loading ...
Loading ...
PIJRON® QUICK REFERENCE GUIDE
FOR INSTALLERS AND TECHNICIANS
Puron refrigerant operates at 50-70 pel_ent higher pressures thari R-22. Be sure that servicing equipment and
replm:ement components ale designed _o operale x_sith Puron
Pmon refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, D(_F 4BA400 or DO'I Bwq00
Pmon systems should be charged widl liquid refrigeront. Use a commel_ial lype melering device in the manifold hose
Manifold sels should be 750 psig high-side and 200 psig low-side wgh 52g psig low-side retard
Use hoses with 750 psig service pressure rating
Leak delectors should be designed to detect HFC refrigerant
Pmon, as other HFC's, ix only compatible with POE oils
Vacuum pumps will not remove moisture from oil
Do not use liquid-line fiber driers with rated working pressures less than g00 psig
Do not ins_atl a suction-line filter drier in liquid line.
POE oils absorb moisture rapidly Do not expose oil to ammsphere
POE oils may cause d_mage Io certain plastics and roofing malelials
Wrap all fifier dliers and service valves wilh wet cloth when brazing
A liquid-line fil_er drier ix required on every umt.
Do not t_se an R-22 TXV
If indoor unit is equipped wilh an R-22 TXV, it must be changed 1o a Pmon TXV
Never open syslem _o atmosphere while it is t_nder a vacuum
When system must be opened for service, break vacuum with dry nitrogen and replace fifier dliers
Do not vent Pumn into gte almosphere.
Do not use capillary tube indoor coils
Observe all warnings_ cautions and boht lext.
© 2003 CAC/BDP 7310 W Mo_ns St, In(fianapolis, iN 46231 [mf×4b02 16 Book/Tab: 1/4,3d12e Catalog No 63FX-4B1