Loading ...
Loading ...
Loading ...
16
Electrical Wiring
(B) Denition and description of SW03
SW03_1
Address setting
mode
0
Automatic address setting or wired controller address setting (default)
1 Code-set address
SW03_2
~
SW03_8
Code-set indoor
unit address
and centralized
controller address
(Note 2)
2 3 4 5 6 7 8
Address of
indoor unit
Address of centralized
controller
0 0 0 0 0 0 0 0# (Default) 0# (Default)
0 0 0 0 0 0 1 1# 1#
0 0 0 0 0 1 0 2# 2#
0 1 1 1 1 1 1 63# 63#
1 0 0 0 0 0 0 0# 64#
1 0 0 0 0 0 1 1# 65#
1 0 0 0 0 1 0 2# 66#
1 1 1 1 1 1 1 63# 127#
Note:
•Set the address by code when connecting the centralized controller or gateway or charge system.
•Address of centralized controller =communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication address
SW03_ 2=ON, address of centralized controller=communication address+64 (applies when
centralized controller is used and there are more than 64 indoor units)
•To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address codes which are set
according to actual address.
•When connecting central controller, gateway or counting system, set address by dip switch.
Special function
1. Emergency switch:
Press the emergency switch in stop condition, indoor unit
operate with AUTO, AUTO SPEED, 24 Setting modes,
pressure the emergency switch in start condition, indoor
unit will stop operation.
2. Temp. consumption:
The heating mode, the temp. compensation range is
6.8°F(-14°C)~32°F(0°C) .
Set the temp. consumption in Heating mode with remote
controller, heating mode ,set 86°F(30°C) as the reference
point, press the sleep butter 7 times, the buzzer ring 2
times, the unit enter temp. consumption condition. Temp.
consumption data=current temp.-22°F(-30°C)
In the cooling mode, the temp.compensation range is
19.4°F(-7°C)~44.6°F(+7°C).
Set the temp. consumption in Cooling mode with remote
controller, cooling mode ,set 73.4°F(23°C) as the reference
point, press the sleep butter 7 times in 5 seconds, the
buzzer ring 2 times, the unit enter temp. consumption
condition. Temp. consumption data=current temp.-9.4°F(-
23°C).
3. Energy saving setting:
In on condition, press the health button 8 times within 5
seconds, buzzer short ring 4 times that the energy saving
setting is valid, if the buzzer rings 2 times that the energy
saving setting is invalid.
4. Compulsive Defrost:
In heating mode, setting high speed ,set temp. is
86°F(30°C), press sleep button for 6 times, buzzer short
ring 3 times, unit enter manual defrost mode.
5. Auto start function:
In on condition, press the sleep button 10 times within 5
seconds, buzzer short ring 4 times stands for enter auto
restart function; press the sleep button 10 times within 5
seconds, buzzer short ring 2 times stands for exit auto
restart function .
The memory information: on/off condition, mode, fan
speed, setting temp., swing position.
6. Room card Function:
Room card function can realize by remote controller.
Press the light button 12 times with remote controller,if
the buzzer rings 4 times that the room card is valid, if the
buzzer rings 2 times that the room card is invalid.
7. Health anion function:
In on condition, press the "HEALTH" button, when
displaying icon
on LCD display, Air conditioner starts
health anion function operation, press the "HEALTH" button
again n to cancel anion function.
Loading ...
Loading ...