*HORIZONTAL VENT SECTIONS: A minimum clearance of 4 1/2" (114mm) to the top and 1 1/2" (38mm) to the
sides and bottom of the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections within
enclosures require a minimum clearance of 11" (279mm) at the top of the vent pipe, see “MINIMUM CLEARANCE
TO COMBUSTIBLE ENCLOSURES” section. Use fi restop spacer W010-3364 (supplied).
*VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. Vertical vent sections within enclosures
require a minimum clearance of 2" (51mm) around the vent pipe. Use fi restop spacer W010-3364 (not supplied).
* When constructing the enclosure allow for fi nishing material thickness to maintain clearances.
IMPORTANT: Before fi nishing in the appliance test the operation using the remote control, cycling it through
all of its different modes, see “OPERATION” section. Should trouble shooting be required, access to the
controls can be made through the pre-fi nishing access panel.
88"
(223.5cm)
MINIMUM
57 3/8"
(145.7cm)
29 3/8"
(74.6cm)*
55 1/4"
(140.3cm)