User Manual - Page 120

For 1311302.

Loading ...
Loading ...
Loading ...
Control Specification SiUS121827E
114 Part 4 Functions and Control
4.9 Outdoor Fan Control
1. Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
2. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 seconds after the compressor stops.
3. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled as
well as normal operation.
4. Fan control when the number of heating room decreases
When the outdoor temperature is more than 10°C (50°F), the fan is turned off for 30 seconds.
5. Fan speed control during forced cooling operation
The outdoor fan is controlled as well as normal operation during forced cooling operation.
6. Fan speed control for POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7. Fan speed control during indoor/outdoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor/outdoor unit
quiet operation.
8. Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
4.10 Liquid Compression Protection Function
Outline The compressor stops according to the outdoor temperature for protection.
Details Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below –12°C (10.4°F).
4.11 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes of accumulated time have passed after the start of the operation, or
ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (B°C (C°F))
Loading ...
Loading ...
Loading ...