11
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
7DEOH$UW&RRO3UHPLHU8QLW6SHFL¿FDWLRQV&RQWLQXHG
6SHFL¿FDWLRQV
System (Model) (Indoor Unit / Outdoor Unit)
LA090HYV3
(LAN090HYV3/LAU090HYV3)
LA120HYV3
(LAN120HYV3/LAU120HYV3)
Dehumidification Rate (pts./hr.) 3.17 3.59
Heat Exchanger
Material and Fin Coating Copper Tube / Aluminum Fin (Gold Fin™ Coating on Outdoor Unit Coil; N/A on Indoor Unit Coil)
Rows / Columns / Fin per inch x Qty. Outdoor Unit: 2 x 28 x 18; Indoor Unit: 2 x 16 x 20
Fan
Indoor Unit Type x Qty. Cross Flow x 1
Outdoor Unit Type x Qty. Propeller x 1
Outdoor Unit Motor Output (W) x Qty. 85 x 1 85 x 1
Outdoor Unit Motor / Drive Brushless Digitally Controlled/Direct
Airflow Rate
IDU Max/H/M/L (CFM) 530 / 424 / 353 / 184 530 / 424 / 353 / 184
ODU Max (CFM) 1,730 1,730
Piping
Liquid (in.) Connection / Pipe Size 1/4 / 1/4 1/4 / 1/4
Vapor (in.) Connection / Pipe Size 3/8 / 3/8 3/8 / 3/8
Condensation Line (OD, ID, in.) 25/32, 19/32 25/32, 19/32
Refrigerant Pre-Charge (oz.) 40.6 40.6
Additional Refrigerant Charge (oz/ft) 0.22 0.22
Pipe Length
6
(Minimum/Maximum) (ft) 9.8/65.6 9.8/65.6
Piping Length
6
(no add’l refrigerant, ft) 24.6 24.6
Max Elevation Difference (ft) 39.4 39.4
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
All power wiring/communication cables are field supplied and are to be minimum 14 AWG, 4-conductor,
stranded, shielded or unshielded (if shielded, must be grounded to chassis at outdoor unit only) and
must comply with applicable local and national codes.
3
Optional Low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
4
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
5
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
6
Piping lengths are equivalent.
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).