INSTALLATION
U.S. 6.00
Canada 450mm (18”)
U.S. 6.00
Canada 450mm (18”)
U.S. 6.00
Canada
203mm (8”)
U.S. 6.00
Canada
203mm (8”)
U.S. 6.00
Canada
203mm (8”)
U.S. 6.00
Canada
203mm (8”)
FLOOR PROTECTION
This heater must have a non-combustible oor protector (UL1618 ember protection) installed beneath it if the oor is of
combustible material. The oor pad or non-combustible surface should be large enough to cover at least the area under
the product and 6 in. (152 mm) beyond the front and beyond each side of the fuel loading and ash removal openings.
Your heater will need a minimum 31” X 38” oor protector. Floor protection must extend under and 2 in. (50.8 mm) to
each side of the chimney tee for an interior vertical installation (see FIGURE 4) This applies to both freestanding heaters
and insert heaters.
Canadian Installations require a minimum of 475 mm [18”] beyond the front of the unit and 203 mm [8”] beyond each
side of the unit. A Floor Protector of 1/4 inch thick is recommended for this installation.
FIGURE 3
THROUGH THE WALL INSTALLATION
FIGURE 4
INTERIOR VERTICAL INSTALLATION