16
INSTALLATION
AS A BUILT-IN FIREPLACE
The gures on this page describe this stoves
installation vented into either a special chase
built outside an outer wall or a false inside wall.
This is especially suited for new construction or
remodeling.
The equipment compartment (sides and rear of
the stove in replace) must be enclosed per the
applicable electrical standards.
NOTE: Floor protection for Built-in raised
hearths requires a continuous
sheet
beneath to
prevent the possibility of embers
falling through
to the combustible oor if cracks or separation
should occur in the nished surface.
This replace insert must be installed with a
continuous chimney liner of 3” or 4” diameter
extending from the replace insert to the top of
the chimney. The chimney liner must conform
to the Class 3 requirements of CAN/ULC-S635,
Standard for Lining Systems for Extending Ma-
sonry or Factory-Built Chimneys and Vents, or
CAN/ULC-S640, Standard for Lining Systems
for New Masonry Chimneys.
The existing replace damper may be removed
or locked into the open position.
The chase dimensions shown are minimums
and must be maintained.
IF THE FIREPLACE HAS BEEN MODIFIED
TO ACCOMMODATE THE FIREPLACE IN-
SERT A METAL TAG SHALL BE ATTACHED
TO THE FIREPLACE.
DO NOT USE MAKESHIFT COMPROMISES
DURING INSTALLATION.
23.75 min
8”
MIN
MANTLE
FACADE
OPENING
214.15” min
20.”12 min.
46” MIN
RAISED HEARTH
SEE “INSERT INSTALLATIONS” FOR
PANEL SURROUND INSTALLATION
6”
MIN.
6”
MIN.
3”
MIN.
3”
MIN.
LISTED
CHIMNEY
CAP
STORM
COLLAR
CHASE CAP
MANTLE
12”
FACING
6”
MAX
10”
THE PANEL SURROUND KIT
D)
ATTACH THE PANEL SURROUND
TO THE PANEL SURROUND TO
THE FACE OF THE FIREPLACE
WITH ONE SCREW.
2.25”
23.75”
6”
MIN.
8”
MIN.
FLOOR PROTECTOR MUST BE
CONTINUOUS WITH NO JOINTS
RAISED HEARTH MUST BE BUILT
OF 8” HOLLOW CONCRETE BLOCKS.
IF CHOOSING TO VENT HORIZONTALLY THROUGH THE WALL, WE RECOMMEND
TERMINATING VERTICALLY WITH AN ADDITIONAL RUN OF AT LEAST 5 FEET.
*
MAY BE DRAWN FROM
ATED CRAWL SPACE.
OUTSIDE AIR
LISTED
CHIMNEY
CAP
*
LISTED
THIMBLE
6”
15.75”
EQUIPMENT
COMPARTMENT
(OPTIONAL VERTICAL INSTALLATION)
L-VENT ONLY
SIDING
5/8” SHEETROCK
(ENTIRE FACADE)
A 1/4” (OR SMALLER) WIRE MESH
SCREEN MUST BE INSTALLED IN
THIS INSTALLATION TO COVER
THE EQUIPMENT COMPARTMENT.
FIGURE 14
FIGURE 15