Installation Manual
Page
36
-One zone system-
-Multi zone by Actuator/Telestat system-
Optional Items
Item #6: HSPS120LT (One zone panel) - This Master One
Zone Panel (Low Temp-Max. 155° F) is utilized when 1
thermostat zone is required in the system. The panel extracts
the heated uid from the boiler and processes the heated
uid to the emitter circuit. Boiler and emitter circuits have
hydraulic separation for independent ow adjustments.
Item #7: HSPS120MTL (Master Pro Integrator Panel -
Zoning by Actuator) - This Master Zoning by Actuator
Panel (Low Temp-Max. 155° F) utilizes primary/secondary
plumbing just like the one zone panels. This panel would be
a great choice when you have multiple zones with emitters
that have the same water delivery temperatures, less than
1800 sqft. total and can bring all the loops to 1 central
manifold. Note: This options requires 1 actuator( Item
#8) for each loop/run of your system (6 Max.) Each zone
must have min. of 600 sqft.
Item #8: Thermo-Electric Zoning Actuator - Actuators
open and close when thermostats call for heat and can
be grouped together for thermostatically controlled zones
with more than 1 loop (there should always be a minimum
of 2 loops per zone). These actuators have a control knob
for manual opening, valve opening/closing indicator and a
device for returning to automatic operation from the manual
position.
Hydronic Manifold - Always use a hydronic manifold
not a potable water manifold for your radiant heating
system. Hydronic manifolds have ow control valves
and site ow gauges. Ideal ow rate of .5 to .8
GPM per loop/run. (Call 1-763-331-3066 for order
assistance.)