SETUP & TESTING
System setting Description
Factory default setting (bold)
and setting range
28. Blast Offset Amount of heating when Heat Blast is initiated. 3°F (1.5°C)
3°F to 5°F (1.5°C to 2.5°C)
37. Stage Rate Accumulation of equipment run time in
equipment staging determination.
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
2
1 to 5 or “OFF” to ignore accumulated
run time.
38. Progressive Recovery Enable or disable progressive recovery. 0: Disable
1: Enable
39. Low Balance Point Outdoor temperature low balance point.
Note: This option is only available if the outdoor
sensor is enabled.
20°F or -8°C
0°F to 60°F (-18°C to 12°C) or OFF to
ignore LBP
40. High Balance Point Outdoor temperature high balance point.
Note: This option is only available if the outdoor
sensor is enabled.
65°F or 14.5°C
0°F to 80°F (-18°C to 22°C) or OFF to
ignore HBP
41. Program Format Enables the 7 day program. 0: 7-Day
1: Non-Prog
54. Change Air Filter Reminder The period displaying the Change Air Filter
reminder.
OFF
1 to 12 months
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
SETUP & TESTING
System setting Description
Factory default setting (bold)
and setting range
55. Change Water Panel
Reminder
The time until the first Change Water Pnl
message is displayed.
OFF
1 to 12 months
56. Humidifier Type Selects the type of humidifier. If humidifier type
is set to Drain-less, then the first reminder is
based on the system setting 55, the second
reminder will activate 3 months later. If
humidifier type is set to Flow through, then the
first reminder is based on system setting 55, the
second reminder will activate 12 months later.
0: Flow through type humidifier
(1 reminder per season)
1: Drain-less type humidifier
(2 reminders per season)
SYSTEM SETUP INSTRUCTIONS (CONTINUED)