Installation and Operation Manual - Legend III
ENGLISH
8.1 Clearances
APPLIANCE CLEARANCES WITH SINGLE
WALL PIPE CONNECTOR
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada USA Canada USA
A
14 ½" (368 mm) 14 ½" (368 mm)
A
7 ½" (191 mm) 7 ½" (191 mm)
B 12" (305 mm) 12" (305 mm) B 12" (305 mm) 12" (305 mm)
C 10" (254 mm) 10" (254 mm) C 8" (203 mm) 8" (203 mm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
13
FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
DISTANCES
13
FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTOR
Canada USA Canada USA
D 18" (457 mm) 18" (457 mm) D 11" (279 mm) 11" (279 mm)
E 20 ¾" (527 mm) 20 ¾" (527 mm) E 20 ¾" (527 mm) 20 ¾" (527 mm)
F 19 ¾" (502 mm) 19 ¾" (502 mm) F 17 ¾" (451 mm) 17 ¾" (451 mm)
8.1.1 With Heat Shield AC02762
14
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
DISTANCES FROM DOUBLE WALL PIPE
CONNECTOR
Canada USA Canada USA
A 3" (76 mm) 3" (76 mm) D 6 ½" (165 mm) 6 ½" (165 mm)
B 3" (76 mm) 3" (76 mm) E 11 ¾" (298 mm) 11 ¾" (298 mm)
C 3" (76 mm) 3" (76 mm) F 12 ¾" (324 mm) 12 ¾" (324 mm)
13
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.
14
Note that to reduce the clearances of an appliance using a single wall pipe connector, the use of a heat shield certied with the single wall pipe
connector to be used as close as 6" (153 mm) from combustible materials must be used. Only in this case, the same clearances as a certied double
wall pipe connector can be used.