Kelvinator Air Conditioning Outdoor unit installation 11
Outdoor unit installation
Refrigerant pipe connection
NOTE:
The connectors used to join the indoor and outdoor
refrigeration pipes must be located outside. They cannot be
located inside or within a wall cavity where refrigerant may
build up in the case of a leak.
Refrigeration pipe length will affect the capacity and energy
efciency of the unit. The nominal efciency is tested based on
the pipe length of 5 meters.
If the installation requires pipe length greater than the
standard 5m, then add additional refrigerant according to the
below table, which also indicates the maximum pipe length
and maximum height difference between indoor and out
door
units.
Please also refer to the below table for discharge and suction
pipe diameter.
Model
Discharge
pipe
diameter
Suction pipe
diameter
Standard
length
(m)
Maximum
length
(m)
Maximum
height
(m)
Additonal
refrigerant
(g/m)
ø 6.35 (1/4") ø 9.52 (3/8")
5 25 10 15
ø 6.35 (1/4") ø 12.7 (1/2")
5 25 10 15
ø 6.35 (1/4") ø 12.7 (1/2")
5 30 20 15
ø 9.52 (3/8") ø 15.9 (5/8")
5 50 25 30
ø 9.52 (3/8") ø 15.9 (5/8")
5 50 25 30
KSV25CRH
KSV25HRH
KSD25HRH
KSV35CRH
KSV35HRH
KSD35HRH
KSV50HRH
KSD50HRH
KSV71CRH
KSV71HRH
KSD71HRH
KSV90HRH
KSD90HRH