5
EN
a side burner, a separate line must be branched o to the side burner unit and enter the side burner
opening at the specied locaon. If the enclosure is to house a propane cylinder, the tank poron of the
enclosure must be venlated according to local codes, and must not have communicaon with the cavity
used to enclose the gas grill. A propane cylinder can not be stored below the gas grill.
BUILT IN CYLINDER ENCLOSURES: Built in cylinder enclosures which completely enclose the cylinder must
have both of the following:
1. At least one unobstructed venlaon opening on the exposed exterior side of the enclosure located
within 5
in
(127mm) of the top of the enclosure. The opening must have a total free area of more than 20 in
2
(130 cm
2
) for a 20 lb (9.1 kg) cylinder and 30 in
2
(195 cm
2
) for a 30 lb (13.6 kg) cylinder.
2. At least one venlaon opening on the exposed, exterior side of the enclosure located 1 in (25.4 mm)
or less from the oor level. The opening must have a total free area of more than 10 in
2
(65 cm
2
) for a 20
lb
(9.1 kg) cylinder and 15 in
2
(100 cm
2
) for a 30 lb (13.6 kg) cylinder. The upper edge must be no more
than 5 in (127 mm) above the oor level.
Every opening must be large enough to permit the entrance of a 1/8 in (3.2 mm) rod.
WARNING!
The cylinder valve(s) must be readily accessible for hand operaon. A door on the enclosure to gain
access to the cylinder valves is acceptable, provided it is non-locking and can be opened without the
use of tools.
The enclosure for the LP-gas cylinder must isolate the cylinder from the burner compartment to
provide shielding from radiaon, a ame barrier, and protecon from foreign material, such as hot
drippings. The enclosure cannot be located directly below the grill.
There must be a minimum clearance of 2 in (51 mm) between the oor of the LP-gas cylinder
enclosure and the ground.
The enclosure must be designed so that the LP-gas cylinder can be connected, disconnected and
the connecons inspected and tested outside the cylinder enclosure. Any connecons that can
be disturbed when installing the cylinder in the enclosure must be accessible for tesng inside the
enclosure.
CYLINDER SIZE OPENING A AREA OPENING B AREA
20 lb (9.1 kg)
20 in
2
(130 cm
2
) 10 in
2
(65 cm
2
)
30 lb (13.6 kg)
30 in
2
(195 cm
2
) 15 in
2
(100 cm
2
)
5” (127 mm)
MAXIMUM
1” (25.4 mm)
MAXIMUM
OPENING
A
OPENING
B
2” (51 mm)
MINIMUM
PARTITION TO ISOLATE
CYLINDER FROM GRILL
NON LOCKING DOOR
34” (864 mm)
RECOMMENDED
5” (127 mm)
MAXIMUM