Inspection
Cleaning
Checking Voltage
Please perform regular visual inspections by following these steps:
Please clean the battery at regular intervals by following these steps:
Examine the external appearance of the battery. The top of the battery and terminals should
be clean, dry, and free of corrosion.
Check battery cables and connections. Replace any damaged cables and tighten any loose
connections.
Disconnect the battery from the charging source or electric load.
Switch the battery to shelf mode using the Power Button.
Dry the battery with a clean cloth and keep the area around the battery clean and dry.
Clean the top of the battery and terminals with a damp cloth or non-metallic brush. A
household cleaner may be used if the battery is extremely dirty.
Ensure the battery is completely dry before switching it to active mode and/or reconnecting
it to the charging source or electric load.
Battery Maintenance
Terminal corrosion may adversely affect the battery performance and present a safety
hazard. Please keep terminals free of corrosion.
During the standard discharging process, the battery is discharged a constant current of 10A
until the battery voltage reaches 41.62V. Safe discharging requires battery temperatures
between -4°F and 140°F (-20°C and 60°C).
Please check the battery voltage periodically to assess battery health. If the battery resting
voltage is under 41.62V in active mode at room temperature, the battery may have been
over-discharged due to self-discharge or parasitic loads. Please stop using the battery until the
fault can be corrected and the battery can be charged.
It is recommended to pair the battery with discharge equipment featuring low voltage
disconnect in the system.