Setting and Using Method
Installation manual 21
• Demand control by analog input control (10 Step)
SW_ STEP
Normal
(V)
Input voltage
range(V)
Cooling Heating
Type of
input
Min Max
Evaporating
Temp. [°C]
Operation
rate
Condensing
Temp. [°C]
Operation
rate
C
0 0 0.4 Comp off
0%
Comp off
0%
Analog
input
1 0.6 1.4 Comp off Comp off
2 1.6 2.4 Comp off Comp off
3 2.6 3.4 11.0 40% 31.3 40%
4 3.6 4.4 9.8 45% 33.3 45%
5 4.6 5.4 9.0 50% 34.5 50%
6 5.6 6.4 7.2 60% 37.5 60%
7 6.6 7.4 5.9 70% 40.4 70%
8 7.6 8.4 5.0 80% 43.1 80%
9 8.6 9.4 4.1 90% 45.6 90%
10 9.6 10 3.1 100% 48.1 100%
D
0 0 0.4 No control - No control -
Analog
input
1 0.6 1.4 3.1 100% 48.1 100%
2 1.6 2.4 4.1 90% 45.6 90%
3 2.6 3.4 5.0 80% 43.1 80%
4 3.6 4.4 5.9 70% 40.4 70%
5 4.6 5.4 7.2 60% 37.5 60%
6 5.6 6.4 9.0 50% 34.5 50%
7 6.6 7.4 9.8 45% 33.3 45%
8 7.6 8.4 11.0 40% 31.3 40%
9 8.6 9.4 Comp off 0% Comp off 0%
10 9.6 10 All off 0% All off 0%
E
0 0 0.4 Comp off 0% Comp off 0%
Analog
input
1 0.6 1.4 11.0 40% 31.3 40%
2 1.6 2.4 9.8 45% 33.3 45%
3 2.6 3.4 9.0 50% 34.5 50%
4 3.6 4.4 7.2 60% 37.5 60%
5 4.6 5.4 5.9 70% 40.4 70%
6 5.6 6.4 5.0 80% 43.1 80%
7 6.6 7.4 4.1 90% 45.6 90%
8 7.6 8.4 3.1
100%
48.1
100%9 8.6 9.4 3.1 48.1
10 9.6 10 3.1 48.1