Loading ...
Loading ...
Loading ...
Setting and Using Method
14 Variable Water Flow Controller Kit
4. Power source input
Error Status
Input_1
Input_2
Input_3
Input_LNO
Reserved
Priority setting
AI_1
Reserved
AO_4
AO_3
AO_2
AO_1
Field Wiring
Power
AC or DC
Power
AC or DC
Operating Status
ڸ
ڹ
ں
ڻ
Dry contact input part
• Input_1,2,3 : Demand control by contact input(3 Step)
• Input_LNO : Low Noise Operation
• Priority setting
Using ʻPriority settingʼ contact signal the priority of command.
(Demand control for external command from DDC vs peak control by LG Centrol controller.)
- Close : Central controller has priority to external signal
- Open : External signal has priority to central controller(default setting)
Analog input part (AI : DC 0 ~ 10V)
AI_1 : Demand control by analog input (10 Step)
Analog output part(AO : DC 0 – 10V, Max 20 mA)
• AO_1 : Connect analog output signal for variable water flow valve.
Digital Output (DDC output AC 1A at 250V source)
• Output error status
• Output operation status
Power must be turned on after the product is wired completely.
Loading ...
Loading ...
Loading ...