Vertical Exhaust Installation
D753I_SVG
7
2
6
5
4
3
1
1. Roof
2. 24 in. [610 mm] Minimum Clearance to Roof/Ground
3. No Screen or Cap
4. Wall
5. 2 in. [50 mm] Minimum
6. Where the exhaust duct pierces a combustible wall or ceil-
ing, an opening must be sized as shown or per local codes.
7. Connect to Dryer
Figure 8
WARNING
To reduce the risk of fire and the accumulation of
combustion gases, DO NOT exhaust dryer air into a
window well, gas vent, chimney or enclosed, unven-
tilated area, such as an attic, wall, ceiling, crawl
space under a building or concealed space of a
building.
W045
A Backdraft Damper, Part No. 58786 (obtain locally),should be
installed in a 4 inch [102 mm] diameter VERTICAL duct system.
This will prevent a backdraft when dryer is not in use, and will
keep the exhaust air in balance within the central exhaust system.
Gas Dryers - Connect Gas Supply Pipe
WARNING
To reduce the risk of gas leaks, fire or explosion:
The dryer must be connected to the type of gas
as shown on nameplate located in the door re-
cess.
Use a new flexible stainless steel connector.
Use pipe joint compound insoluble in L.P. (Lique-
fied Petroleum) Gas, or Teflon tape, on all pipe
threads.
Purge air and sediment from gas supply line be-
fore connecting it to the dryer. Before tightening
the connection, purge remaining air from gas line
to dryer until odor of gas is detected. This step is
required to prevent gas valve contamination.
Do not use an open flame to check for gas leaks.
Use a non-corrosive leak detection fluid.
Any disassembly requiring the use of tools must
be performed by a suitably qualified service per-
son.
W316
1. Make certain your dryer is equipped for use with the type of
gas in your laundry room. Dryer is equipped at the factory for
Natural Gas with a 3/8 inch NPT gas connection.
NOTE: The gas service to a gas dryer must conform
with the local codes and ordinances, or in the ab-
sence of local codes and ordinances, with the latest
edition of the National Fuel Gas Code ANSI Z223.1/
NFPA 54 or the CAN/CSA-B149.1 Natural Gas and
Propane Installation Code.
Natural Gas, 1000 Btu/ft
3
[37.3 MJ/m
3
], service must be supplied
at minimum 5.0 inch water column pressure to maximum 10.5
inch water column pressure.
For proper operation at altitudes above 2000 feet [610 m] the nat-
ural gas valve spud orifice size must be reduced to ensure com-
plete combustion. Refer to Table 4 .
Natural Gas Altitude Adjustments
Altitude Orifice Size
Part
Numberfeet [m] #
inches
[mm]
2,000 [610] 41 0.0960
[2.44]
D503776
Table 4  continues...
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
22 Part No. D516119ENR3