Specifications
Other components are necessary for a complete
installation - see System Essential Components section.
Zoneline
®
Vertical Unit Nomenclature
The Zoneline vertical unit is identified by a model number defining the type of unit, cooling capacity, and electrical information.
When specifying or ordering the Zoneline Vertical unit the use of this nomenclature will assure receiving the correct unit.
Electric resistance heat Cool only Heat pumps
230/208 Volt Models AZ75E09DAC AZ75E12DAC AZ75E18DAC AZ75W09DAC AZ75W12DAC AZ75W18DAC AZ75H09DAC AZ75H12DAC AZ75H18DAC
Features
BTUH 9,500/9,300 11,700/11,500 17,500/17,200 9,500/9,300 11,700/11,500 17,500/17,200 9,500/9,300 11,700/11,500 17,500/17,200
E.E.R. (BTUH/Watt) 10.5/10.5 10.7/10.7 10.0/10.0 10.5/10.5 10.7/10.7 10.0/10.0 10.5/10.5 10.7/10.7 10.0/10.0
Dehumidification (pints/hr.) 2.7 3.6 5.0 2.7 3.6 5.0 2.7 3.6 5.0
Universal Heater (kW) 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0 N/A N/A N/A 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0
Heating Cap (BTUH) N/A N/A N/A 8,400/8,200 10,900/10,700 15,700/15,500
COP @ 4 3.6 3.3 3.1
Voltage (V) 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208
Unit Width (in.) 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8
Unit Depth (in.) 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8 23-1/8
Unit Height (in.) 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4
Indoor CFM (Hi/Med/Low) 0.4" ESP 310/260/230 375/315/250 550/475/440 310/260/230 375/315/250 550/475/440 310/260/230 375/315/250 550/475/440
265/277 Volt available by special order.
265/277 Volt specifications similar to 230 Volt.
EXAMPLE
Listed by
Underwriters'
Laboratories.
Electric resistance heat Heat pumps
265 Volt Models
AZ75E09EAC AZ75E12EAC AZ75E18EAC AZ75H09EAC AZ75H12EAC AZ75H18EAC
Features
BTUH 9,500 11,700 17,500 9,500 11,700 17,500
Watts 950 1095 1750 950 1095 1750/1720
E.E.R. 10.0 10.7 10.0 10.0 10.7 10.0/10.0
Cool Amps 3.7 4.7 7.2 3.7 4.7 7.2
Dehumidification (pints/hr.) 2.7 3.6 5.0 2.7 3.6 5.0
SHR .70 .67 .71 .70 .67 .71
Reverse Cycle (BTUH) 8,400 10,900 15,700
COP @ 4 3.6 3.3 2.5
Indoor CFM (Hi/Med/Low) 0.4" ESP 310/260/230 375/315/250 550/475/440 310/260/230 375/315/250 550/475/440
Ship Wt. 152 165 174 152 165 174
Net Wt. 141 154 163 141 154 163
265/277 Volt available by special order.
A Z 7 5 E 0 9 D A C
Chassis series
75=vertical
Unit type
E= cooling with electric
resistance heat
H= heat pump with electric
resistance heat
W=Cool only
Zoneline
®
packaged
terminal unit
Voltage/Phase/Frequency
D= 230/208 Volt, single phase, 60 Hz
E= 265 Volt, single phase, 60 Hz
Heater
configuration
A= Universal heater
See power
connection kits
section
Nominal cooling capacity
09=9,500 BTUH cooling
12=11,700 BTUH cooling
18=17,500 BTUH cooling
Special Features
C= corrosion protection
19
geappliances.com
Zoneline
®
warranty
What is covered
Limited one-year warranty
For one year from date of original purchase, we will provide,
free of charge, parts and service labor on site to repair or
replace any part of the Zoneline unit that fails because of
a manufacturing defect.
Limited additional four-year sealed refrigerating
system warranty
For four years from the date of original purchase, we will
provide, free of charge, parts and on site service labor to
repair or replace any part of the sealed refrigerating system
(the compressor, condenser, evaporator and all connecting
tubing) that fails because of a manufacturing defect.
Limited 2nd through 5th year parts warranty
For the second through the fifth year from date of original
purchase, General Electric will provide, free of charge, parts
that fail as a result of a manufacturing defect. Parts covered
are fan motors, switches, thermostat, heater, heater protectors,
compressor overload, solenoids, circuit boards, auxiliary
controls, thermistors, frost controls, capacitors, varistors, and
indoor blower bearing. This is a limited parts-only warranty,
and does not include labor or transportation to and from the
service shop.
What is not covered
Service trips to your site to teach you how to use the product.
Improper installation.
If you have an installation problem, or if the air conditioner
is of improper cooling capacity for the intended use, contact
your dealer or installer. You are responsible for providing
adequate electrical connecting facilities.
• Replacement of fuses or resetting of circuit breakers.
In commercial locations, labor necessary to move the
unit to a location where it is accessible for service by an
individual technician.
Failure of the product resulting from modifications to
the product or due to unreasonable use including failure
to provide reasonable and necessary maintenance.
Failure or damage resulting from corrosion due to installation
in an environment containing corrosive chemicals.
Failure or damage resulting from corrosion due to
installation in a coastal environment, except for models
treated with special factory-applied anti-corrosion
protection as designated in the model number.
Damage to product caused by improper power supply
voltage, accident, fire, floods or acts of God.
Incidental or consequential damage to personal property
caused by possible defects with this air conditioner.
Warrantor: General Electric Company. Louisville, KY 40225
This warranty is extended to the original purchaser and any
succeeding owner for products purchased for use within the
USA and Canada. In Alaska, the warranty excludes the cost of
shipping or service calls to your site.
Some states do not allow the exclusion or limitation of incidental
or consequential damages. This warranty gives you specific
legal rights, and you may also have other rights which vary
from state to state. To know what your legal rights are in your
state, consult your local or state consumer affairs office or
your state’s Attorney General.
Equipment used as a primary source for heating or cooling is an integral part of
the building in which it is installed. Proper application is essential for satisfactory
performance over a wide range of operating conditions. It is strongly recommended
that a professional engineer determine proper application.
If this unit is a replacement unit, its specifications and performance may differ from
those of the unit it is replacing. For that reason, we again strongly recommend that
a professional engineer determine proper application.
GE has a policy of continuous improvement on its products and reserves the right to
change materials and specifications without notice.
Staple sales slip or cancelled check here. Proof of original purchase date is needed to obtain service under warranty.
For service in the U.S., call 800-GE-CARES. In Canada, contact: Gordon Williams Corp. at 1-888-209-0999.