System Essential Components and Installation
positioned on the platform in
the closet with the outdoor side
facing the wall plenum opening
(remove the side panel if a side
installation is to be made) and
secured to the plenum with six
field supplied screws (stainless
recommended).
Level the case using the four
leveling legs and, using the holes
in the bottom of the case as
guides, drill holes in the mounting
platform to secure the case to the platform. Use four field-
supplied bolts, washers and nuts to secure the case to the
mounting platform. Do not tighten the bolts to the point of
distorting the case.
Failure to secure the case to the platform may result in
excessive unit vibration and increased noise level. Install
the unit into the case, either through the front or side panel
opening. With the unit in position in the case, replace the front
panel and, if removed, the side panel. Ground the unit to the
case by installing the front unit-to-case hex bolt and/or the
case-to-unit side screw.
The drain connection is made by connecting a 90
o
PVC
elbow to the units female 3/4 NPT drain connector. The other
end of the elbow is used to run the drain to either the internal
or external drain.
The unit is shipped with a secondary drain hole. This drain hole
is shipped open and must either be plugged or connected to
an independent drain system. If a secondary drain system is
used, attach a 90° schedule 40 PVC elbow to the secondary
drain hole directed toward the secondary drain system. If a
secondary drain system is NOT used, install a 3/4" schedule 40
PVC plug to cap the hole.
A 10" diameter flange on the top of the unit is used to connect
to field supplied, insulated, flexible or rigid transition duct with
an adjustable ring clamp.
Flexible duct may be used for transitions only. Rigid duct must
be used for 90
o
bends and tees. Do not use flexible duct for
unsupported runs of five feet or more.
Power Connection Kit
The ZVAC units have a universal heater assembly that is
capable of producing electric resistance heat that can operate
on a 15-amp, 20-amp, or 30-amp circuit. The amount of
resistance heat is determined by the selection of the correct
power connection kit. This is the same type of connection
used by GE for years in the Premium and Deluxe series of the
Zoneline units.
Units installed on 230 or 208-volt circuits may be line cord
connected by plugging the line cord into a wall-mounted
receptacle in the enclosure closet or directly connected.
All ZVAC units come with a unit mounted junction box
to contain the wiring connections if a direct connection
installation is required. The same power connection kit is
used for line cord connection or to make a direct connection.
Instructions for making a direct connection on 230 or 208-volt
circuits are included in the unit installation instructions.
Units installed on a 265-volt circuit must be direct connected
in accordance with National Electrical Code. All ZVAC units
come with a unit mounted junction box to contain the wiring
connections when direct connection installation is made.
Return air grille, access panel or
louvered closet door
The return air from the room to the unit
may enter the enclosure closet through
one of four ways. A louvered door may be
installed on the closet to allow return air to
enter the closet through the louvers. When
a louvered door is used, the filter would be
installed in the filter bracket on the front
panel of the unit.
A wall-mounted access panel may be
used instead of the louvered door. In this
installation access to the unit is through a wall-mounted
access panel rather than a door. The return air is through the
panel. The access panel, model RAVRG1, requires a 28" wide by
48" high cutout in the wall and there is a filter bracket behind
the grille louvers.
The return air grille, model RAVRG2, may also be used and
is designed to be installed in a 20 3/8" by 20 3/8" cutout in a
flush closet door. In this installation, a filter can fit into the
bracket in the RAVRG2.
A field-supplied return air grille, with a minimum dimension of
20" by 20", may be used if mounted in a cutout in the door or
wall. When employing this method for return air, the filter is
installed in the bracket mounted on the unit.
230/208 Volt Line Cord Connected Units
Power Connection RAK3152 RAK3202 RAK3302
Heater kW 2.55/2.09 3.45/2.82 5.0/4.09
Heater Amps 11.0/10.0 15.0/13.6 21.7/19.7
Minimum Circuit 15 20 30
Recommended
Protective Device
15 Amp Time Delay
Fuse or Breaker
20 Amp Time Delay
Fuse or Breaker
30 Amp Time Delay
Fuse or Breaker
Plug Configuration 15 Amp Tandem
20 Amp
Perpendicular
30 Amp
Large Tandem
265 Volt Direct Connected Units
Power Connection RAK5157 RAK5207 RAK5307
Heater kW 2.55 3.45 5.0
Heater Amps 9.7 13.1 18.9
Minimum Circuit 15 20 30
Recommended
Protective Device
15 Amp Time Delay
Fuse or Breaker
20 Amp Time Delay
Fuse or Breaker
30 Amp Time Delay
Fuse or Breaker
230/208 Volt Direct Connected Units
Power Connection RAK4157 RAK4207 RAK4307
Heater kW 2.55/2.09 3.45/2.82 5.0/4.09
Heater Amps 11.0/10.0 15.0/13.6 21.7/19.7
Minimum Circuit 15 20 30
Recommended
Protective Device
15 Amp Time Delay
Fuse or Breaker
20 Amp Time Delay
Fuse or Breaker
30 Amp Time Delay
Fuse or Breaker