ENGLISH
1. RS-485 communication line specification: 0.75mm
2
or above 2C shield, product to product: 200M,
total length: 1km
2. FT-10 communication line: Refer to the following table.
* Nod to node distance (max): 250m, maximum distance: 450m
* AWG: American Wire Gauge
Cable Type Line thickness (AWG) Diameter
TIA 568A Category 5 cable 24 0.5mm
Belden 88471 (PVC jacket) or 16 1.3mm
equivalent cable
Belden 85102(Tefzel jacket) or 16 1.3mm
equal cable
Level IV cable 22 0.65mm
JY(st)Y 2x2x0.8 20.4 0.8mm
Communication line specification