• Initial display order
• Example) ARUN060GSS4
Order No Note
4~12 Model capacity
1 Cooling only
2 Heat pump
38 380V
46 460V
22 220V
1 Standard
5 Cold temperature area
6 Tropical
7 2 22 1
22
ENGLISH
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
* Dip switch 3 can be OFF except when installing the only 4 series in-
door units (named ARNU***4).
Mode Function Option Value Action
Remarks
Content
Display1
Content
Display2
Content Display3
Content Display4
Implement Display5
Installation
Cool & Heat
Selector
oFF
op1~
op2
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Static pres-
sure com-
pensation
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Night low
noise
oFF
op1~o
p12
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
ODU
address
-
-
0~255
set
the
value
Change
the set
value
Blank
Save in
EEPROM
Snow re-
moval &
rapid defrost
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Target
pressure
adjusting
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
DIP-SWITCH 7 - Segment
SW01C ( : confirm)
SW02C ( : backward)
SW03C ( : forward)
SW04C (
: cancel)
SW01D (reset)
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to im-
prove communication.
!
The Procedure of Automatic Addressing
• Automatic addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
on 7-segment LED after completing setting
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
and Automatic addressing is completed normally.
Automatic addressing start
Waiting 3 minutes
Power On
Press RED Button for 5 s
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
OK
YES
NO Check the connections
of communication cable
= 88
Setting the function
Select the mode/function/option/value using ‘’, ‘’ Button and con-
firm that using the ‘’ button after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
SW01C ( : confirm)
SW02C ( : backward)
SW03C ( : forward)
SW04C (
: cancel)
SW01D (reset)
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
-
Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ……, CH06 : Indicated as numbers of connected indoor units)
[Heat Pump (MAIN PCB)]
Checking the setting of outdoor units
Checking according to dip switch setting
- You can check the setting values of the Master outdoor unit from the
7 segment LED.
The dip switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condi-
tion. (For example, represents R410A 10HP)